Filling / Venting; Start-Up; Running Checks; Shutdown - salmson S Serie Manuel D'installation Et Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

  ENGLISH  
 
Check following points : 
 Pump flow is always higher than authorized continuous minimum flow, 
 Pump never runs dry, 
 Normal leakage of the shaft seal is controlled, 
  Surface  temperature  bearings  housings  is  lower  than  the  maximum 
admissible surface temperature in selected ATEX zone, 
 Pressure on discharge side of the pump is lower than pump maximum 
allowable working pressure. 
 Set alarm and stop trips of sensors. 
 
In every cases check : 
 Quality of electrical connections, 
 Protection devices are installed, 
 Auxiliary piping are connected, 
 Flanges connections, 
 Suction line and pump casing are filled with fluid, 
 Motor direction of rotation is correct, 
 Coupling alignment is correct, 
 Oil level was checked and greasing of ball bearings has been done, 
 Coupling guard is installed. 
 
8.2 FILLING / VENTING 
During pre‐commissioning, pump casing must be filled with fluid. Other 
starts will not need further actions. See chapter 8.6 PRIMING TIME. 
Take  precautionary  measures  when  manipulating  dangerous  or 
 
polluting fluids. Wearing individual protective devices is necessary. 
The operator must know potential hazards. 
 
8.3 START‐UP 
Check  that  the  automatic  greasing  cartridge  is  screwed  in 
 
mechanical  seal  housing  and  that  it  is  switched  on  in  position  12. 
(supply of grease during 12 months). Check its grease content if it is not 
a new cartridge : 
 
 Open slightly the discharge valve (only if no auxiliary venting pipe is 
installed). 
 Open all valves in suction line. 
 Switch on the pump  
  Wait  until  pump  has  primed  and  note  this  priming  time.  Then  close 
the  discharge  isolating  valve  and  measure  max  pressure  (zero  flow). 
Compare this pressure to the shutoff pressure available on the hydraulic 
curve. 
 
In  order  to  avoid  overheating  of  the  liquid  inside  the  pump  the 
 
pump  should  not  work  more  than  20  to  30  seconds  against  a 
closed discharge valve. 
 If expected pressure is reached then open progressively the discharge 
valve. 
 If there is no liquid delivered or if discharge pressure is  too low
then see chapter "trouble shooting". 
 
 
16
8.4 RUNNING CHECKS 
During  operation  of  pump  in  duty  conditions  (capacity,  head, 
temperature, ...) the following points must be checked : 
 
 Check and note pump duty point. If necessary convert pressure value 
from bar indicated on the pressure gauge to mwc : 
HMT
 = (P
 x 100) / (SG x 9,806) with SG= fluid Specific Gravity. 
mce
bar
 Check and note current consumption on each phase of the motor. 
 Check calibration of motor protections. 
 Check temperature of ball bearings (on bearing housing surface). 
  Check  flexible  coupling  alignment  after  several  pump  starts  (only  for 
concerned pumps variants). 
 Check tightening of flanges fastening bolts. 
 Check there is no leakage and no abnormal running noise. 
 
When pumping hot fluids, the definitive coupling alignment should 
be  done  only  when  system  nominal  temperature  is  reached  and 
stabilized. See chapter 7.1.4 COUPLING ALIGNMENT 
 
Check the surface temperature on the bearing bracket and on the 
pump  casing.  Check  pumped  fluid  temperature.  Alarm  and  stop 
trips  settings  should  be  done  according  those  values.  Refer  to  specific 
sensors IOM before adjusting those trips. 
 
8.5 SHUTDOWN 
Before the pump is stopped close the discharge isolating valve. 
Ensure  that  the  pump  runs  in  that  condition  no  more  than  few 
seconds. 
When  the  pump  has  come  to  a  standstill  :  close  the  suction  isolating 
valve. If the pump is equipped with auxiliary systems such as a quench, 
heating system, flushing, external lubrication, etc ... it must be closed at 
the last step. 
 
If temperature is likely to drop below freezing point, pump casing 
and auxiliary connected systems should be completely drained or 
otherwise  protected.  For  prolonged  shut‐downs  an  adapted  rust 
protective  coating  should  be  applied  to  the  inside  and  outside  of  the 
pump. 
 
Pumping  explosive,  toxic  or  polluting  fluids  :  make  sure  that  all 
necessary actions were taken to avoid the creation of a hazard for 
people or environment during drainage operations. 
 
Products  which  are  sent  back  to  Salmson  must  be  drained  and 
cleaned.  Pumped  fluid  should  be  completely  removed  from  the 
pump. 
 
8.6 PRIMING TIME 
The suction line drains down into the tank between two starts. The flow 
does  not  appear  immediately  after  pump  start  but  only  after  a  few 
seconds : it is called priming time. 
 
Piping  will  be  design  in  order  to  allow  free  air  extraction  without 
counter‐pressure (discharge back to tank, vent valve, discharge line 
to an atmospheric exhaust ...). 
Even if the mechanical seal is equipped with a quench behind the 
stationary  seat,  priming  time  will  be  limited  to  5  minutes.  If 
discharge pressure doesn't rise after this time, stop the pump and check 
piping system. 
For an ATEX application, it may happen that the alarm temperature 
 

Publicité

Chapitres

Table des Matières
loading

Table des Matières