temperature  depends  on  the  ATEX  temperature  class  and  must  not 
exceed the values indicated in the ATEX additive attached to the pump. 
The  shaft  seal  and  bearings  temperature  rise  due  to  the  minimum 
permitted flow rate are taken into account. 
The fluid temperatures indicated are given accordingly : 
 
 
T1  350°C 
T2  270°C 
T3  175°C 
T4  110°C 
T5  75°C 
T6  need SALMSON approval 
 
A  temperature  sensor  must  be  installed  in  pump  casing  to  check 
 
that fluid temperature never  exceeds the  permitted temperature 
during priming time. 
Motor overload trips should be correctly calibrated. 
If  pump  is  installed  in  dirty  or  dusty  environment,  it  is  necessary  to 
proceed with regular cleanings. 
2.9.3
BUILD UP OF EXPLOSIVE MIXTURE 
Ensure  that  pump  casing  and  mechanical  seal  chamber  are 
 
correctly vented and that pump will not turn dry. 
 
Self‐priming  pump  are  designed  to  ensure  that  an  amount  of  liquid 
always  remains  inside  the  pump  casing  even  after  pump  stop.  This 
allows the pump to prime and never run dry. After a long term stop, it 
will  be  necessary  to  check  that  there  is  still  enough  liquid  inside  the 
pump (some liquids may evaporate due to external temperature) before 
starting up the pump again. 
 
Make sure that the pump runs with filled‐in suction and discharge lines 
to avoid build up of an explosive atmosphere. In addition, it is essential 
that auxiliary sealing systems are properly filled and working. 
To avoid potential hazards creation from fugitive emissions of vapor or 
gas to atmosphere the surrounding area should be correctly ventilated. 
2.9.4
PREVENTING LEAKAGE 
The pump must only be used to handle the liquids for which it has 
 
been defined. 
 
If  the  pump  is  installed  outdoor,  make  sure  liquid  containing  parts  are 
drained and/or protected against freezing. 
 
If  leakage  of  liquid  to  the  atmosphere  can  result  in  a  hazard  then  a 
leakage detection sensor should be installed. 
2.9.5
COMPLETE UNIT 
ATEX certification for a complete unit according to ATEX Directive 
 
94/9/CE  is  given  according  to  lower  protection  level  of  the 
integrated component. This comment applies particularly to the electric 
motor protection. 
2.9.6
PUMP  UNIT  DELIVERED  WITHOUT  MOTOR  / 
WITHOUT SENSORS 
If  a  partial  delivery  is  required  (electric  motor,  flexible  coupling, 
 
coupling  guard  or  sensor  not  supplied),  an  integration  certificate 
will be established. 
It will be the integrator's responsibility to supply missing parts in order 
to fulfill ATEX requirements for the complete machine. 
2.9.7
COUPLING GUARD 
The  coupling  guard  used  in  a  potentially  ATEX  atmosphere  shall 
 
meet following requirements : 
 
Consist of non‐sparking material (e.g brass), 
Must be made of antistatic material, 
Must  be  designed  in  such  a  way  that  the  rotating  parts  will 
not come in contact with any part of the guard after a choc. 
2.9.8
MAINTENANCE TO AVOID HAZARD 
When  a  pump  is  used  in  a  potentially  ATEX  atmosphere  it  is 
necessary to check regularly the following parameters and respect 
a  maintenance  plan  to  ensure  that  the  equipment  runs  in  perfect 
technical conditions. 
 
Following regular checks are mandatory : 
No leakage of the shaft seal, 
Ball bearings temperature (on bracket housing surface), 
No cavitations and no abnormal running noises, 
Correct position of isolating valves and function of motorized 
valves. 
If some parts are worn or working in bad conditions the pump must be 
stopped immediately and put in safety until maintenance operations are 
performed. Origin of default(s) should be eliminated. 
2.9.9
PREVENTING SPARKS CREATION 
Necessary  measures  must  be  taken  to  avoid  sparks  creation  in  case  of 
external impact. 
 
Base  plate  and  pumpset  elements  must  be  properly  grounded.  Ensure 
continuity between components of the group. 
 
It applies to : 
Pump hydraulics, 
Coupling guard, 
Motor frame, 
Baseplate. 
 
The threaded hole or the earthing plate located on the base plate should 
be used to make proper earthing. 
 
3
TRANSPORT AND STORAGE 
3.1 SAFETY MEASURES 
Never rest below a suspended load. 
 
Keep a safe distance while the load is being transported. 
Check  equipment  weight  and  choose  slings  and  other  lifting 
devices  accordingly.  Lifting  equipments  should  be  in  good 
conditions. 
Adjust the length of the lifting devices so that pump or/and pumps 
set is moved horizontally. 
Lifting lugs or  eyebolts that are sometimes attached to the pump 
or  to  the  motor  should  not  be  used  to  lift  a  complete  pump  set. 
They  should  be  used  only  to  lift  pump  parts  during  dismantling 
operations. 
Use the lifting points that are mentioned on the pump set or refer 
to following information. 
3.2 DELIVERY 
After  reception  of  goods,  the  delivered  items  must  be  inspected 
for  damage.  Check  that  all  parts  are  present  (check  description 
and  quantities  against  delivery/shipping  documents).  If  any  parts  are 
damaged,  missing  or  if  transportation  damage  is  visible,  this  should  be 
noted on the freight documentation or on the delivery note. 
Do not separate attached documentation from the pump. 
Unpack  the  good  and  eliminate  packaging  according  environmental 
requirements. 
Do  not  remove  caps  from  pump  flanges  if  pump  will  not  be  installed 
immediately. 
 