Parameter Meaning
Low alarm limit (ALarm Low)
If the process value at the analog input 1 (in.1, cold store) goes below this limit:
1. the alarm message
if
v
Chapter 8 "Alarm and error messages"
2. if available (see Chapter 1 "Identifying the instrument version")
Alarm signal via relay
as set under
High alarm limit (ALarm High)
If the process value from analog input 1 (in.1, cold store) goes above this limit:
1. the alarm message
if
v
Chapter 8 "Alarm and error messages"
2. if available (see Chapter 1 "Identifying the instrument version")
Alarm signal via relay
as set under
Alarm hysteresis
The selected hysteresis is below
appears on the display,
= on (factory-set).
or alarm buzzer,
.
appears on the display,
= on (factory-set).
or alarm buzzer,
.
5 Parameter level
or above
.
26
Value range
from...factory-set...to
For AL.F = 0 and 1:
-200 ... -50 ... +500
°C
For AL.F = 2 and 3:
0 ... +500 °C
For AL.F = 0 and 1:
-328 ... -58 ... +932
°F
For AL.F = 2 and 3:
0 ... +900 °F
For AL.F = 0 and 1:
-200 ... 50 ... +500
°C
For AL.F = 2 and 3:
0 ... +500 °C
For AL.F = 0 and 1:
-328 ... 122 ... +932
°F
For AL.F = 2 and 3:
0 ... +900 °F
0.0 ... 1.0 ... 50.0
°C or
0.0 ... 1.8 ... 90.0
°F