8.1 Troubleshooting

What is happening?
Communication with the unit inter-
rupted after setup data was transmit-
ted.
2009-04-10
The flash memory of the data logger
is faulty.
The chip for the real-time clock
is faulty.
Cause / Remedy
Interface settings of the unit and PC do
not match.
h
Compare the interface settings made
in the setup file with those of the unit.
h
The instrument must be returned to JUMO for repair.
Information
v
v
8 Alarm and error messages
Chapter 7.1 "Setup program"
Chapter 5.8 "Interface"