Parameter Meaning
Time 1
(defrosting time 1)
Time 2
(defrosting time 2)
Time 3
(defrosting time 3)
Time 4
(defrosting time 4)
Defrosting limit (defrost SetPoint)
The present process value of the evaporator is acquired via analog input 2 and
compared with the defrosting limit. If this is exceeded, defrosting is ended.
Defrosting delay
After power ON, defrosting is started after a defrosting delay time has elapsed.
Afterwards, the normal defrosting cycle is resumed. If defrosting delay=0, no defrosting
is started after power ON.
Drip-off time (defrost drip-off time)
After the end of defrosting, the evaporator can drip off within this time.
2009-04-10
Hours and minutes can be separated by a decimal point.
The digit behind the decimal point represents a 10-minute step.
Example: 23.5 signifies: 23:50 hrs
0.1 signifies: 00:10 hrs
:
H
If a time has been entered, defrosting takes place
on a daily base.
If all times are set to off, then
Value range
from...factory-set...to
switched off: off
0.0... 23.5 hrs
is effective again.
0.0...10.0...35.0 °C or
32.0...50.0...95.0 °F
0...30...99 minutes
0...3...99 minutes
5 Parameter level
21