Technical data

Analog input 1
Designation
and 2
RTDs
Pt100 EN 60751
Pt1000 EN 60751
PTC
KTY1X-6
KTY2X-6
resistance 10 — 3500 Ω customer table
Measuring current for Pt100: 2 mA, for Pt1000, KTY2X-6, KTY1X-6 and resistance: 0.2 mA
Lead compensation is adjustable via the parameter Lead compensation resistance
The total resistance at the analog input (probe resistance + selected value for or.1 or or.2) must not exceed the
following values: Pt100: 314
Input resistance
Sampling time
Input filter
Measuring current
Temperature offset
Special features
1.) A valid customer table must be entered through the setup program and switched over to
2009-04-10
Measuring range
-200 to +600°C
-200 to +600°C
-50 to +100 °C
-50 to +150 °C
Ω,
Ω,
Pt1000: 3140
KTY2x-6: 2235
≥ 100kΩ
R
IN
250msec
1st order digital filter; filter constant adjustable from 0.1 to 99.9sec
with Pt100: 0.2mA, with Pt1000, KTY2X-6, KTY1X-6 and resistor: 0.02mA
adjustable via the parameters
temperature indication switchable to °F (Fahrenheit)
Tolerance
in % of measuring range span,
temperature effect
0.05% (±0.4°C),100ppm/°C
0.05% (±0.4°C),100ppm/°C
0.5% (±0.75°C),100ppm/°C
0.5% (±1°C),100ppm/°C
1
0.075% (±2.6Ω),100ppm/°C
and KTY1x-6: 3400
and
in the instrument.
7 Technical data
Detection of ...
probe
short-
circuit
yes
yes
yes
yes
yes
and
.
.
probe
break
yes
yes
yes
yes
yes
35