Parameter Meaning
Baud rate
9.6 means: 9600 bps
19.2 means: 19200 bps
38.4 means: 38400 bps

5.9 Data logger

The data logger saves 11263 data sets to a ring memory which overwrites the oldest data with the most recent ones when the
memory is full. The data can be read out and processed.
v
Chapter 7.1 "Setup program"
Delete all entries from the data logger:
h
Press
(> 3 seconds), enter code 822 and acknowledge with
Recording interval for data logger
The most recent data are recorded every 5 minutes (ex-factory).
Examples for a continuous recording, without overwriting the old data.
rEC
1 min
5 min
15 min
60 min
120 min
If 0 minutes is set, the data logger is switched off.
2009-04-10
Recording duration
7 days 19 hours
39 days (1 month, 9 days)
117 days (4 month)
469 days (1year 3 months)
938 days (2 years 6 months)
H
The real time clock time is
buffered without a power
supply for approx. 20 days.
If this buffer time is excee-
ded, recording continues
with the date 01.01.07
(ex factory).
5 Parameter level
Value range
from...factory-set...to
9.6, 19.2, 38.4
0...5...120 minutes
29