Parameter Meaning
Lead compensation resistance, analog input 1 (offset resistance 1)
This value serves to compensate the resistance of the probe cable; it is dependent on
the cable length.
For an optimum temperature measurement, the resistance value of the probe cable
must be entered here.
A
A measurement error will occur if the total resistance at the analog input
(probe resistance + selected value for or.1) exceeds the following values:
Pt100: 314
Probe at analog input 2, in 2-wire circuit
It measures the evaporator temperature.
stands for customer-specific linearization, settable through a table of values in
the setup program.
Temperature offset, analog input 2 (offset temperature 2)
Process value offset
2009-04-10
Ω,
Ω,
Pt1000: 3140
KTY2x-6: 2235
Ω,
KTY1x-6: 3400
.
5 Parameter level
Value range
from...factory-set...to
0.0 ... 0.0 ... 99.9
switched off:
Pt100:
Pt1000:
KTY1X-6:
KTY2X-6:
or
-50.0...0.0...50.0 °C
or
-90.0...0.0...90.0 °F
13