JUMO eTRON M 100 Notice De Mise En Service page 66

Masquer les pouces Voir aussi pour eTRON M 100:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2009-04-10
Parameter Meaning
Hysteresis
For cooling and freezing, the hysteresis lies above the selected setpoint.
For the "Cooling + Heating" function, the hysteresis is above or below the selected
setpoint, like a window function.
Cooling / Freezing
T/°C
Analog input 1 (cold store)
9
= 1°C
SP = 8 °C
Relay
energized
de-energized
Low setpoint limit (SetPoint Low)
SP can be set down to this low limit.
High setpoint limit (SetPoint High)
SP can be set up to this high limit.
T/°C
Analog input 1
9
=1
SP = 8 °C
7
t
Relay
energized
Cooling
de-energized
t
1
Relay
energized
de-energized
5 Parameter level
Cooling and Heating
=1
Heating
16
Value range
from...factory-set...to
0.0...1.0...50.0 °C
or
0.0...1.8...90.0 °F
t
t
t
-200 ... -50 ... SP.H-10
°C or
-328 ... -58 ... SP.H-18
°F
SPL+10 ... 50 ... +500
°C or
SPL+18 ... 122 ... +932
°F