7
Commissioning
Parameter setting with E82ZBC keypad
Vector control
7.2.2
Vector control
The following instructions apply to controllers equipped with a standard−I/O function
module and a three−phase AC motor which has been selected according to a power−based
assignment.
Switch−on sequence
1.
Connect keypad
2.
Ensure that controller inhibit is active after mains connection
3.
Switch on the mains
4.
The keypad is in "Disp" mode after approx. 2 s and indicates the
output frequency (C0050)
5.
6.
Go to the ALL menu
Change to the f mode to configure the basic settings for your
7.
drive
8.
Adapt the terminal configuration to the wiring (C0007)
Lenze setting: −0−, i. e.
E1: JOG1/3 fixed setpointselection
E2: JOG2/3
E3: DCB DC brake
E4: CW/CCW rotation
9.
Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz
10.
Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz
11.
Set the acceleration time T
Lenze setting: 5.00 s
12.
Set the deceleration time T
Lenze setting: 5.00 s
13.
Activate the operating mode "vector control" (C0014 = 4)
Lenze setting: Linear V/f characteristic control (C0014 = 2)
14.
Adapt the voltage/current range for the analog setpoint selection
(C0034)
Lenze setting: −0−, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)
15.
Enter the motor data
A
Rated motor speed (C0087)
Lenze setting: 1390 rpm
B
Rated motor current (C0088)
Lenze setting: Depending on the controller
C
Rated motor frequency (C0089)
Lenze setting: 50 Hz
D
Rated motor voltage (C0090)
Lenze setting: Depending on the controller
E
Motor cosj (C0091)
Lenze setting: Depending on the controller
170
(C0012)
ir
(C0013)
if
l
Comment
Terminal X3/28 = LOW
The USEr menu is active
Blinking on the display: 0050
Set the DIP switch on the standard I/O to the same
range (see Mounting Instructions for the standard
I/O)
See motor nameplate
Enter the value for the motor circuit configuration
(star/delta) selected!
Enter the value for the motor circuit configuration
(star/delta) selected!
EDK82EV903 DE/EN/FR 5.1