5.4
Standard devices in the power range of 55 kW
5.4.1
Mains connection
(
Stop!
ƒ
ƒ
ƒ
0
1
4
2,5 Nm
T1
T2
22.1 lb-in
PE
PE
+UG
L1 L2 L3
+UG, -UG
PE
EDK82EV903 DE/EN/FR 5.1
Standard devices in the power range of 55 kW
Only connect the controller to the permitted mains voltage (^ Technical
data). A higher mains voltage destroys the controller!
Some controllers may only be actuated with a mains choke or mains filter.
This requirement can differ with regard to operation at rated power and
operation at an increased rated power.
The leakage current to earth (PE) is > 3.5 mA. In accordance with
EN 61800−5−1 a fixed installation is required. The PE conductor has to be
designed double.
3/PE AC 400V
PE
PE
+UG
L1 L2 L3
-UG
M8
L1, L2, L3
15 Nm
+UG, -UG
132 lb-in
PE
3/PE AC 400V
E82EV453K4:
2-6 Nm (17.7-53.1 lb-in)
L1, L2,
E82EV553K4:
L3
6-12 Nm (53.1-106.2 lb-in)
L1 L2 L3
3
l
-UG
M8
15 Nm
132 lb-in
0
Connection for mains choke
1
Connection for footprint mains filter
2
Connection for built−on mains filter
3
Connection for braking unit (^ Documentation of braking unit)
4
Temperature monitoring connection for mains filter (thermal contact)
Z1
Mains choke/mains filter
l
Electrical installation
Mains connection
3/PE AC 400V
L1
L2
3
L3
N
PE
l
2
PE
L1' L2' L3'
Gerät / Load
PE
PE
+UG
L1 L2 L3
-UG
M8
L1, L2, L3
15 Nm
+UG, -UG
132 lb-in
PE
L1
L2 L3
Z1
T1
4
J>
T2
3
+UG
L1
L2
PE
L3
-UG
Z1
3
l
8200vec289
147