5
Electrical installation
Motor connection
5.3.4
Motor connection
{
Danger!
ƒ
ƒ
1
f
g
g
2,5 Nm
k
22.1 lb-in
T1
T2
PES
PE
PES
PE
Cable cross−sections U, V, W, PE
8200 vector
E82xV153K4B
E82xV223K4B
Ñ Ñ Ñ Ñ Ñ Ñ Ñ Ñ Ñ Ñ
Ñ Ñ Ñ Ñ Ñ Ñ Ñ Ñ Ñ Ñ
E82xV303K4B
Ñ Ñ Ñ Ñ Ñ Ñ Ñ Ñ Ñ Ñ
146
All control terminals only have basic insulation (single isolating distance)
after connecting a PTC thermistor or a thermal contact.
Protection against accidental contact in case of a defective isolating
distance is only guaranteed through external measures, e. g. double
insulation.
2
PE
k
e
T1
2,5 Nm
T2
22.1 lb-in
PE
U
V
W
PES
PES
PES
PTC
PES
J>
M
PE
3~
Use low−capacitance motor cables! (core/core £ 140 pF/m, core/shield £ 230 pF/m)
The shorter the motor cable, the better the drive behaviour!
PES
HF shield termination by PE connection through shield clamp.
T1, T2
Terminals of motor temperature monitoring with PTC thermistor or thermal
contact (NC contact).
Lay a separate cable (shielded) to X2/T1 and X2/T2 for motor temperature
monitoring.
Activate motor temperature monitoring with C0119 (e.g. C0119 = 1)!
Lay the control and mains cables separately from the motor cable!
Ñ Ñ Ñ Ñ Ñ Ñ Ñ Ñ Ñ Ñ
Ñ Ñ Ñ Ñ Ñ Ñ Ñ Ñ Ñ Ñ
Ñ Ñ Ñ Ñ Ñ Ñ Ñ Ñ Ñ Ñ
l
M 6
U, V, W,
5 Nm
PE
44 lb-in
U
V
W
PE
T1
T2
PES
M
3~
2
mm
10
16
25
8200vec285
AWG
8
6
3
EDK82EV903 DE/EN/FR 5.1