Supply and fan connection at the controller for a mains voltage of 400 V/500V
4.4
Supply and fan connection at the controller for a mains voltage of 400 V/500V
4.4.1
Mains connection
ƒ Both, the master and the slave must be supplied!
L1
L2
M8
25-30 Nm
L1, L2,
L3
221-264 lb-in
Fig.9-5
Fuses and cable cross-sections for the mains connection
Type
EVF9381-EVV210
EVF9381-EVV240
EVF9381-EVV270
EVF9381-EVV300
EVF9382-EVV210
EVF9382-EVV240
EVF9382-EVV270
EVF9382-EVV300
EVF9383-EVV210
EVF9383-EVV240
EVF9383-EVV270
EVF9383-EVV300
EDKVF9383 DE/EN/FR 1.0
Stop!
The user is responsible for sufficient strain relief!
0
PE
L3
+UG
-UG
BR1
BR2
PE
U
40 mm
M6
PE
15-20 Nm
133-176 lb-in
Mains connection example
BR1, BR2
Brake resistor can only be operated with the variants V270 and V300
For connection see System Manual of 9300 vector
Master terminals
Slave terminals
Fuse
Master
315A
315A
400 A
1)
Multiple conductor; both conductors must have the same cross-section
2)
Lenze recommends to use fuses of the gRL utilisation category
Observe the national and regional legislation
Electrical installation
V
W
L1
L2
M8
25-30 Nm
L1, L2,
L3
221-264 lb-in
Installation to EN 60204-1
2)
L1, L2, L3 [mm
Slave
Master
150
315A
1)
2 × 50
150
315A
1)
2 × 50
240
400 A
1)
2 × 95
Mains connection
1
PE
L3
+UG
-UG
BR1
BR2
PE
U
40 mm
M6
PE
15-20 Nm
133-176 lb-in
2
]
PE [mm
Slave
Master
Slave
150
95
1)
2 × 50
150
95
1)
2 × 50
240
150
1)
2 × 95
4
V
W
9300VEC035
2
]
95
95
150