ALL OPERATIONS DESCRIBED IN THIS SECTION MUST BE PERFORMED BY QUALIFIED PERSONNEL
ONLY.
Our Company assumes no liability for damages caused by incorrect connections or operations not
contained in this manual.
UPS S
TORAGE
The storage site must meet the following requirements:
Temperature:
Degree of relative humidity:
P
RELIMINARY INFORMATION
UPS Models
Nominal power
Operating temperature
Max relative humidity in operation
Max installation height
Net dimensions
Shipping dimensions
Net weight
Shipping weight
Power loss at nominal resistive load
(pf=0.9) and with charged batteries
(1)
Installation site fan flow rate for
heat removal
(2)
Current dispersed to ground
Degree of protection
Cable input
(1) 3.97 B.T.U./h = 1 kcal/h
(2) Use the following formula to calculate air flow: Q [mc/h] = 3.1 x P diss [kcal/h] / (t a - t e ) [°C]
P diss is power dissipation expressed in kcal/h in the installation site for all installed equipment.
ta= room temperature, te=external temperature. Increase the value derived by 10% to account for losses.
An example of flow is shown in the table, with (t a - t e )=5°C and with nominal resistive load (pf=0.9).
Notes: The formula applies when ta > te ; if not, the installation requires a conditioner).
(3) The load dispersion current is added to that of the UPS on the ground protection conductor.
INSTALLATION
-
UP
-25°÷60°C
30÷95% max
60KVA
60kVA
(W x D x H)
190 kg
214 kg
2.61 kW
2245 kcal/h
8910 B.T.U./h
1400mc/h
(3)
80KVA
80kVA
0 - 40 °C
90 % (without condensation)
1000 m at nominal power
(-1% power for every 100 m above 1000 m)
max 4000 m
500 x 850 x 1600 mm
625 x 900 x 1720 mm
200 kg
224 kg
3.65 kW
3140 kcal/h
4074 kcal/h
12460 B.T.U./h
16170 B.T.U./h
2000 mc/h
< 300 mA
IP20
at bottom rear
- 69 -
100KVA
125KVA
100kVA
125kVA
650 x 830 x 1600 mm
780 x 945 x 1745 mm
220 kg
250 kg
244 kg
274 kg
4.75 kW
5,32 kW
4575 kcal/h
18160 B.T.U./h
2600mc/h
3100 mc/h