UTPUT LINE FUSES
Normal fuses (gL-gG)
Thermal magnetic switches (C Curve)

R.E.P.O.

This isolated input can be used to remotely switch off the UPS in case of emergency.
The UPS is supplied with "Remote Emergency Power Off" (R.E.P.O.) terminals short-circuited by a jumper (see "Communications
area view"). To manage emergency shutdown, replace the jumper with the selected normally closed stop device contact. Connect
using double insulation wiring.
In case of an emergency, the stop device opens the R.E.P.O. control and the UPS goes into stand-by mode (all power stages off)
and the load is completely disconnected.
The R.E.P.O. circuit is self-powered with SELV circuits. Therefore, an external voltage supply is not required. When closed (normal
condition), a current of 15mA max circulates.
/
THERMAL MAGNETIC SWITCHES
Output protections (recommended values for selectivity)
60-80-100KVA
In (Nominal current)/7
In (Nominal current)/7
- 81 -
125KVA
In (Nominal current)/4
In (Nominal current)/4