ALL THE OPERATIONS DESCRIBED IN THIS SECTION ARE TO BE PERFORMED EXCLUSIVELY BY
QUALIFIED STAFF.
The company declines all liability for damage caused by incorrect connections or operations not
described in this manual.
S
UPS
TORING THE
The storage room must respect the following conditions:
Temperature:
Relative humidity:
P
REPARING FOR INSTALLATION
P
I
RELIMINARY
NFORMATION
UPS models
Rated power
Working temperature
Max. relative humidity during operation
Max. height of installation
W x D x H
Weight (w/
batteries)
Power dissipated at rated resistive
load (pf=0.9) and with battery as buffer
*
Power dissipated at rated distortion
load (pf=0.7) and with battery charged *
Flow rate of fans for removing heat
from installation room **
Current leak to earth ***
Isolation protection
Cable input
*
3.97 B.T.U./h = 1 kcal/h
** The following formula can be used to calculate the fan capacity: Q [mc/h] = 3.1 x P diss [kcal/h] / (t a - t e ) [°C]
P diss is the dissipated power of all the installed apparatus at the installation premises expressed in kcal/h.
ta= environmental temperature, te= external temperature. To account for leaks, increase the value obtained by 10%.
The table shows an example of the fan capacity with (t a - t e )=5°C and with nominal resistive load (pf=0.8).
(N.B.: The formula applies if ta>te; otherwise an air conditioner should be installed).
*** The dispersion current of the load is added to the dispersion current of the UPS on the earth protection conductor.

INSTALLATION

B
AND THE
ATTERY
0°÷40°C (32°÷104°F)
max. 95%
10 kVA
10000 VA
0.65 kW
560 kcal/h
2218 B.T.U./h
0.50 kW
430 kcal/h
1710 B.T.U./h
300 mc/h
B
OX
12 kVA
12000 VA
90 % (non-condensing)
1000 m at rated power
(-1% Power for every 100 m above 1000 m)
max 4000 m
440 x 850 x 1320 mm
315 Kg
320 Kg
0.76 kW
654 kcal/h
2594 B.T.U./h
0.58 kW
500 kcal/h
1980 B.T.U./h
355 mc/h
From bottom / on rear
- 68 -
15 kVA
15000 VA
0 ÷ 40 °C
325 Kg
0.90 kW
774 kcal/h
3071 B.T.U./h
3924 B.T.U./h
0.69 kW
594 kcal/h
2355 B.T.U./h
3070 B.T.U./h
410 mc/h
< 7 mA
IP20
20 kVA
20000 VA
330 Kg
1.15 kW
989 kcal/h
0.90 kW
775 kcal/h
545 mc/h