EN
Terminal
Connection
20
Shared
21
24 V
Safety device power
supply
22
0 V
23
24 V
24 V accessories power
supply
24
0 V
25
24 V - 15 W
24 V - 15 W orange
light output
26
0 V
27
9 V - 24 V
9 V or 24 V low voltage
supply input
28
0 V
29
EOS O
30
Shared
Motor end limit
31
EOS F
32
1
Motor
33
2
34
24VAC
Transformer
35
6.2. Description of the various peripherals
Warning
The peripheral cables must be secured using the cable clamps supplied.
6.2.1. Photoelectric cells - Fig. 19
Warning
It is compulsory to install photoelectric cells WITH AUTO-TEST P07 =
3 if:
• remote control of the mechanism with gate not visible is used,
• automatic closing is activated ("P01" = 1, 3 or 4).
There are three possible types of connection:
A - without autotest: programme parameter "P07" = 1.
B - with autotest: programme parameter "P07" = 3.
• Allows an automatic test to be carried out to check the operation
of the photoelectric cells each time the gate moves.
• If the operating test result is negative, the gate cannot be moved
until the operating mode changes to deadman operation (after 3
minutes).
C - BUS: programme parameter "P07" = 4.
Remove the bridge between terminals 19 and 20 then programme param-
eter "P07" = 4.
Attention
Auto-programming must be repeated after the cell BUS has been
connected.
6.2.2. Reflex photoelectric cell - Fig. 20
Warning
It is compulsory to install photoelectric cells WITH AUTOTEST P07 = 2
if:
• remote control of the mechanism with gate not visible is used,
• automatic closing is activated ("P01" = 1, 3 or 4).
Without autotest: programme parameter "P07" = 1.
With autotest: programme parameter "P07" = 2.
• Allows an automatic test to be carried out to check the operation
of the photoelectric cell each time the gate moves.
• If the operating test result is negative, the gate cannot be moved
until the operating mode changes to deadman operation (after 3
minutes).
7
Comments
Permanent if auto-test
not selected, controlled if
auto-test selected
1.2 A max for all accesso-
ries on all outputs
Compatible batteries 9.6 V
and 24 V
At 9 V, degraded operation
At 24 V, normal operation
6.2.3. Orange light - Fig. 21
Program parameter "P12" according to the desired operating mode:
• No warning prior to gate movement: "P12" = 0.
• With 2 s warning prior to gate movement: "P12" = 1.
6.2.4. Videophone - Fig. 22
6.2.5. Aerial - Fig. 23
Connect the antenna cable to terminals 7 (conductor) and 8 (braid).
6.2.6. Safety edge - Fig. 24
Only active during closing.
L
For a safety edge active when opening, use the programmable safety input
and programme parameter "P10" = 1.
Attention
The auto-test is mandatory for connecting any active safety edge, to
ensure that the installation is compliant with the standards in force.
Safety edge with auto-test, part no. 9019611: programme parameter
"P08" = 2.
• Allows an automatic test to be carried out to check the operation
of the safety edge each time the gate moves.
• If the operating test result is negative, the gate cannot be moved
until the operating mode changes to deadman operation (after 3
minutes).
Attention
If the safety edge is removed, it is essential to create the bridge be-
tween terminals 17 and 18.
6.2.7. 24 V battery - Fig. 25
1) Position and tighten the battery power supply management card.
2) Position the batteries.
3) Make the connections.
For more details, refer to the 24 V battery instructions.
Normal operation: nominal speed, accessories functional.
Life: 5 cycles/24 hrs
6.2.8. 9.6 V battery - Fig. 26
Downgraded mode: constant reduced speed (no slowing at end limit), 24V
accessories inactive (including cells).
Life: 5 cycles/24 hrs
6.2.9. Area lighting - Fig. 27
For class I lighting, connect the earth wire to the earth terminal on the
base.
Attention
The earth wire must always be longer than the live and neutral wires in
case of detachment.
Several lights may be connected provided the total power does not ex-
ceed 500 W.
7. ADVANCED PARAMETER SETTING
7.1. Browsing the parameter list
Press ...
Access and exit the parameter setting menu
Navigate the parameters and codes list:
• short press = normal scroll through individual pa-
rameters
• press and hold = scroll rapidly through parameters
C onfirm:
• the parameter selection
• the parameter value
to...