Pedestrian opening amplitude
Values
1 to 9
2: 80 cm
Comments
1: minimum pedestrian opening
...
9: maximum pedestrian opening (approximately 80% of
the gate's total travel)
P07
Cell safety input
Values
0: inactive
1: active
2: active with autotest via test output
3: active with autotest via power supply switching
4: bus cells
Comments
0: the safety input is not taken into account.
1: safety device without autotest; it is essential to check
that it is operating correctly every 6 months.
2: the autotest is run on the device for each operating
cycle via the test output, reflex photocell application
with autotest.
3: the autotest is run on the device for each operating cy-
cle via power supply switching of the cell power supply
output (terminals 21 and 22).
4: bus cells application.
P08
Safety edge safety input
Values
0: inactive
1: active
2: active with autotest
Comments
0: the safety input is not taken into account.
1: safety device without autotest; it is essential to check
that it is operating correctly every 6 months.
2: the autotest is run on the device for each operating
cycle via the test output.
P09
Programmable safety input
Values
0: inactive
1: active
2: active with autotest via test output
3: active with autotest via power supply switching
Comments
0: the safety input is not taken into account.
1: safety device without autotest.
2: the autotest is run on the device for each operating
cycle via the test output.
3: the autotest is run on the device for each operating cy-
cle via power supply switching of the cell power supply
output (terminals 21 and 22).
P10
Programmable safety input - function
0: active closing
Values
1: active opening
2: active closing + dangerous moving area accessible to
public
3: all movement disabled
Comments
0: the programmable safety input is only active when
closing.
1: the programmable safety input is only active when
opening.
2: the programmable safety input is only active when clos-
ing and, when activated, the gate cannot be opened.
3: emergency stop application; if the programmable safety
input is activated, the gate cannot be moved.
9
P11
Programmable safety input - action
Values
0: stop
1: stop + partial reversal
2: stop + complete reversal
Comments
0: emergency stop application, compulsory if P10=3
disabled if a safety edge is connected to the program-
mable safety input
1: recommended for safety edge application
2: recommended for cell application
P12
Orange warning light
0: no warning
Values
1: with 2 s warning prior to movement
Comments
If the gate opens onto a public right of way, the "with
warning" configuration must be selected: P12=1.
P13
Area lighting output
Values
0: inactive
1: controlled operation
2: automatic + controlled operation
Comments
0: the area lighting output is disregarded.
1: the area lighting is remotely controlled.
2: the area lighting is remotely controlled when the gate
is stationary + the area lighting comes on automatically
when the gate is moving, and remains on when it stops
moving for the duration of the time delay programmed
in parameter "P14".
P13=2 is compulsory for operation in automatic
mode.
P14
Area lighting time delay
Values
0 to 60 value x 10 s = time delay value)
6: 60 s
Comments
If value 0 is selected, the area lighting goes out as soon as
the gate stops moving.
P15
Auxiliary output
Values
0: inactive
1: automatic: gate open indicator light
2: automatic: timed bistable
3: automatic: one-touch
4: controlled: bistable (ON-OFF)
5: controlled: one-touch
6: controlled: timed bistable
Comments
0: the auxiliary output is not taken into account.
1: the gate indicator light is off when the gate is closed,
flashing when the gate is moving and on when the gate
is open.
2: output activated when movement starts, during
movement then deactivated at the end of the time delay
programmed in parameter "P16".
3: one-touch at contact when movement starts.
4: operation changes as follows each time the memorised
button on the radio control point is pressed: ON, OFF,
ON, OFF...
5: one-touch at contact by pressing the memorised button
on the radio control point.
6: output activated by pressing the memorised button on
the radio control point then deactivated at the end of
the time delay programmed in parameter "P16".