6.2. Description of the various additional devices

Warning
The peripheral cables must be secured using the cable clamps
supplied.
6.2.1. Photoelectric cells - Fig. 18
Warning
It is compulsory to install photoelectric cells WITH AUTOTEST P07
= 3 if:
• remote control of the mechanism with gate not visible is used,
• automatic closing is activated ("P01" = 1, 3 or 4).
Three types of connection are possible:
A - without autotest: programme parameter "P07" = 1.
B - with autotest: programme parameter "P07" = 3.
• Allows an automatic test to be carried out to check the operation of
the photoelectric cells each time the gate moves.
• If the operating test result is negative, the gate cannot be moved
until the operating mode changes to deadman operation (a er 3
minutes).
C - BUS: programme parameter "P07" = 4.
Remove the bridge between terminals 19 and 20 then programme param-
eter "P07" = 4.
Attention
Auto-programming must be repeated a er the cell BUS has been
connected.
6.2.2. Reflex photoelectric cell - Fig. 19
Warning
It is compulsory to install photoelectric cells WITH AUTOTEST P07
= 2 if:
• remote control of the mechanism with gate not visible is used,
• automatic closing is activated ("P01" = 1, 3 or 4).
Without autotest: programme parameter "P07" = 1.
With autotest: programme parameter "P07" = 2.
• Allows an automatic test to be carried out to check the operation of
the photoelectric cell each time the gate moves.
• If the operating test result is negative, the gate cannot be moved
until the operating mode changes to deadman operation (a er 3
minutes).
6.2.3. Orange light - Fig. 20
Programme parameter "P12" according to the required operating mode:
• No warning prior to gate movement: "P12" = 0.
• With 2 s warning prior to gate movement: "P12" = 1.
7
Comments
1.2 A max for all acces-
sories on all outputs
Compatible with 9.6 V
and 24 V batteries or
solar supply
At 9 V, degraded oper-
ation
At 24 V, normal operation
6.2.4. Videophone - Fig. 21
Attention
Not operational using solar power.
6.2.5. Antenna - Fig. 22
Connect the aerial cable to terminals 7 (conductor) and 8 (braid).
6.2.6. Safety edge - Fig. 23
Attention
Not operational using solar power.
Only active during closing.
For a safety edge active when opening, use the programmable safety
input and programme parameter "P10" = 1.
Attention
The autotest is mandatory for the connection of any active safety
edge to ensure that the installation is compliant with the standards
in force.
Safety edge active with autotest, ref. 9019611: programme param-
eter "P08" = 2.
• Allows an automatic test to be carried out to check the operation of
the safety edge each time the gate moves.
• If the operating test result is negative, the gate cannot be moved
until the operating mode changes to deadman operation (a er 3
minutes).
Attention
If the safety edge is removed, it is essential to create the bridge
between terminals 17 and 18.
6.2.7. 24 V battery - Fig. 24
1) Position and tighten the battery power supply management card.
2) Position the batteries.
3) Make the connections.
For more details, refer to the 24 V battery instructions.
Normal operation: nominal speed, accessories functional.
Battery life: 5 cycles/24 hrs
6.2.8. 9.6 V battery - Fig. 25
Degraded operation: speed reduced and constant (no slowing at end limit),
24 V accessories inactive (including cells).
Battery life: 5 cycles/24 hrs
6.2.9. Solar kit - Fig. 26
Adjust the length of the cable connecting the motor to the battery housing.
It should be as short as possible to prevent voltage drops.
5 m cable provided with the solar kit.
Join wires of the same colour to prevent polarity reversal.
6.2.10. Area lighting - Fig. 27
For class I lighting, connect the earth wire to the earth terminal on the
base of the motor.
Attention
The earth wire must always be longer than the live and neutral
wires in case of detachment.
Several lights may be connected provided the total power does not exceed
500 W.