SECTION II: INSTALLATION AND
MAINTENANCE
II.1
UNIT DESCRIPTION
II.1.1
CONSTRUCTION FEATURES
Patented polyvalent system.
Load-bearing structure in galvanised and RAL 9018 painted sheet
steel, coated on the inside with sound-absorbing material, divided into:
soundproofed technical compartment for housing the compressors,
the electrical board and the main components in the refrigerant circuit.
Aeraulic compartment for housing the heat exchange coils, the
motor-driven fans and the pump assembly accessory if present.
Hermetic, Scroll-type rotary compressors, complete with internal
thermal protection and crankcase heater activated automatically when
the unit stops (as long as the power supply to the unit is preserved).
Double electric axial fan with external rotor, equipped with internal
thermal protection and complete with protection grille.
Proportional electronic device for the pressurised and continuous
regulation of the fan rotation speed down to an external air temperature
of -10°C when operating as a chiller and up to an external air
temperature of 40°C when operating as a heat pump.
Stainless steel plate heat exchangers on the primary and secondary
water circuits, complete with closed cell polyurethane foam rubber
insulation and antifreeze electric heaters.
Differential pressure switch on all heat exchangers.
Air side exchanger comprised of a copper pipe coil flared into
aluminium fins with "corrugated" design in order to increase heat
exchange efficiency.
Male threaded water connections.
Refrigerant circuit realised with annealed copper piping (EN 12735-
1-2) and welded with silver alloy. Complete with 2 cycle inversion
valves, charge connections, high and low pressure switch, 2
thermostatic valves, 4 solenoid valves, a drier filter, 2 liquid receivers, a
gas separate, a humidity indicator, 3 non-return valves and a safety
valve (for models 130).
Primary and secondary water circuit made from annealed copper
piping (EN 12735-1-2) and welded with silver alloy. The primary water
circuit also comes complete with:
pump, safety valve (3 bar), pressure gauge, expansion tank, manual
bleed valves and drainage valves.
Secondary water circuit made from annealed copper piping (EN
12735-1-2) and welded with silver alloy, complete with differential
pressure switch.
Compatible control with AdaptiveFunction on the primary
circuit regulation.
Unit with IP24 level of protection.
The unit is complete with the R410A refrigerant charge.
II.1.2
AVAILABLE INSTALLATIONS
Standard – Installation without pump (only available for model 133).
Pump P1 – Installation with pump on primary circuit.
Pump P2 – Installation with pump with increased static pressure on
primary circuit for model 133 (available as factory fitted accessory).
Tank & Pump ASP1 – Installation with pump on primary circuit and water
buffer tank (only available for model 133). The inertial water buffer tank is
installed on the water circuit delivery pipe.
Tank & Pump ASP2 – Installation with increased static pressure on
primary circuit pump and water buffer tank for model 133 (available as a
factory fitted accessory). The inertial water buffer tank is installed on the
water circuit delivery pipe.
IOM_EQP1X_117a133_208094_200901_ES-EN-FR-DE-IT
SECTION II: INSTALLATION AND MAINTENANCE
II.1.3
ELECTRICAL BOARD FEATURES
Electrical board accessible by opening the front panel, conforming
with current IEC standards, and which can be opened and closed with a
suitable tool.
Complete with:
electrical wiring arranged for power supply 400V-3ph+N-50Hz
auxiliary power supply 230V-1ph-50Hz drawn from the main power
supply;
general isolator, complete with door interlocking isolator;
automatic compressor protection switch;
automatic pump protection switch (only available for model 133);
protection fuse for auxiliary circuit;
compressor power contactor;
pump power contactor (only available for model 133);
unit remote controls.
Programmable electronic board with microprocessor, controlled by
the keypad inserted in the machine.
This electronic board performs the following functions:
regulation and management of the set points for inlet water
temperature; cycle inversion; safety timer delays; circulating pump;
compressor and system pump hour-run meter; of pressure defrost
cycles; electronic anti-freeze protection which cuts in automatically
when the machine is switched off; and the functions which control the
operation of the individual parts making up the machine;
complete protection of the unit, automatic emergency shutdown and
display of the alarms which have been activated;
compressor protection phase sequence monitor
unit protection against low or high phase power supply voltage;
visual indication of the programmed set points via the display; of the
in/out water temperature via the display; of the alarms via the display;
and of cooling/heat-pump operating mode via display;
self-diagnosis with continuous monitoring of the functioning of the unit;
user interface menu;
alarm code and description;
alarm history management (menu protected by manufacturer
password).
The following is memorised for each alarm:
date and time of intervention (if the KSC accessory is present);
alarm code and description;
inlet/outlet water temperatures when the alarm intervened;
alarm delay time from the switch-on of the connected device;
compressor status at moment of alarm;
Advanced functions:
configured for serial connection (KR S485, KFTT10, KBE, KBM,
KUSB accessory);
possibility to have a digital input for remote management of the
double set point (contact
HITECSA
possibility to have an analogue input for the scrolling set-point via a
4-20mA remote signal (contact
configured for management of time bands and operation parameters
with the possibility of daily/weekly operating programs (KSC accessory);
check-up and monitoring of scheduled maintenance status;
testing of the units assisted by computer;
self-diagnosis with continuous monitoring of the functioning of the unit;
Adaptive Function on the regulation of the primary circuit.