Press the MODE key in order to access the submenu.
!
ALARM
Prg
MODE
ON
OFF
Use the DOWN key to run through the submenus until reaching the
priority submenu.
!
ALARM
I.7.5.2
Prg
ON
OFF
By pressing the MODE key, the cursor moves down, making it possible
to change the priorities.
By using the DOWN key, it is possible to select one of the three
priorities available:
priority given to hot water from the main
MAIN PROBE
exchanger (condenser/evaporator)
priority given to hot water from the secondary
RECOVER PROBE
exchanger (recovery)
ONLY RECOVER
"Only recover" function on
!
ALARM
Prg
ON
OFF
IOM_EQP1X_117a133_208094_200901_ES-EN-FR-DE-IT
Analog inputs:
MODE
B: 1
12.0 C
B: 2
7.0 C
Probe priority
RECOVER PROBE
MODE
Select the probe
priority
Probe priority
RECOVER PROBE
MODE
Select the probe
priority
In order to confirm the priority selected, keep the Prg key pressed down
for 2 seconds. The initial screen appears on the display.
Prg
I. 7.5.2 Keypad-modifiable variables
The keypad-modifiable variables are as follows:
Function
Cooling set point
Heating set point
Recovery set-point
Remote Automatic/Select
Password
I.7.6
MENU NAVIGATION
To access the available menus, press the Prg key for 3 seconds. With
the UP and DOWN keys it is possible to scroll through the following
menus.
Prg
42
SECTION I: USER
!
ALARM
> Setpoints menu
Probe menu
Prg
Condensing control
Rem.Auto/Select
ON
OFF
Regulation
Default value
-5 ÷ 25°C
12°C
25 ÷ 48°C
40°C
25 ÷ 48°C
40°C
N
Technical Assistance
Set-Point Menu
!
ALARM
> Setpoints menu
Probe menu
Prg
Condensing control
Rem.Auto/Select
ON
OFF
MODE