4.5
TEST MENU
PRESS
0......9
The internal Switch2 must be set in the unlocked position to enter parameters
within this menu. (§ - 3.4.1)
The following parameters can be set within this menu:
OFFSET
SPAN
0......9
CALIB 0
FLOW
END
Fluid Control Systems
TEST MENU
ENTER
SIMULTANEOUSLY FOR 5 SECONDS
Offset adjustment (4 mA).
Span adjustment (20 mA).
Flow zero-point adjustment.
Entering the flowrate to be simulated. The
outputs will react in accordance to this input.
Return to the operation mode and storage of
the new parameters for CALIB 0, OFFSET
and SPAN. If the OFFSET/SPAN values are
inappropriate the device will revert to
"OFFSET" and new values must be entered.
30
SECTIONS
4.5.1
4.5.2
4.5.3
4.5.4
8045