Type 8791
Functions
10.1.1.
DIR.CMD
-
effective sense of direction of the position controller set-
point value
Use this function to set the effective sense of direction between the input signal (INPUT) and the set-point
position of the actuator.
Factory settings: DIP switch set to OFF (ascending)
DiP switches
Position
1
ON
OFF
Table 14:
DIP switches 1
The effective sense of direction (DIR.CMD) can be changed only via DIP switch 1 in the positioner.
Set-point position
Fig. 11:
DIR.CMD graph
Function
Reversal of the effective sense of direction of the set-point value
(DIR.CMD)
Set-point value (20 – 4 mA corresponds to position 0 – 100 %),
descending
Normal effective sense of direction of the set-point value
(Set-point value 4 – 20 mA corresponds to position 0 – 100 %),
ascending
ascending
descending
Input signal
(INPUT)
english
33