Type 8791
Technical Data
8.2.
factory settings of the positioner
8.2.1.
functions can be activated via dip switches
function
CUTOFF
CHARACT
DIR.CMD
Table 3:
Factory settings; Functions can be activated via DIP switches
8.2.2.
functions can be activated via communications software
function
INPUT
DIR.ACTUATOR
SPLITRANGE
X.LIMIT
Function deactivated
X.TIME
Function deactivated
X.CONTROL
SAFEPOSITION
SIGNAL ERROR
BINARY INPUT
Function active
OUTPUT
Function active
Table 4:
Factory settings; Functions can be activated via communications software
parameter
Sealing function below
Sealing function above
Select characteristic
Effective direction set-point value
parameter
Set-point value input
Effective direction actual value
Signal split range below
Signal split range above
Stroke limit below
Stroke limit above
Actuating time Open
Actuating time Closed
Dead band
Open amplification factor
Close amplification factor
Safety position
Sensor break detection set-point value
Binary input function
Operating principle of binary input
Norm signal output: Parameter
Norm signal output: Type
value
2 %
98 %
FREE
increasing
value
4 ... 20 mA
increasing
0 %
100 %
0 %
100 %
(1 s) values determined by X.TUNE
(1 s) values determined by X.TUNE
After implementation of RESET: 1 s
1,0 %
(1) values determined by X.TUNE
(1) values determined by X.TUNE
After implementation of RESET: 1
0 %
OFF
Safety position
Normally open contact
Position
4 ... 20 mA
english
23

Publicité

Table des Matières
loading