3.11 Adjustment of the regulation actions

3.11.1 Manual adjustment of the P-I-D
While the autotune procedure is perfectly satisfactory in most cases, it may sometimes be
necessary to touch up the adjustments, if for example the regulation is modified or if a very
fine adjustment is desired.
Before you modify the adjustments, we strongly recommend recording the current values so
that they can if necessary be restored. Change only one parameter at a time, in small steps,
and observe the reaction of the regulation. Since each of the parameters influences the
others, it is very easy to make mistakes.
Guide to actions
Action
Symptom
Proportional,
Slow response, Large
slow
overshoot or oscillation
Integral
Slow response, Instability or
oscillation
Derivative
Slow response, Large
overshoot
NOTE: These terms designate the adjustments necessary to optimize regulation by the
STATOP series 15 . If you are not familiar with them, not to worry! The autotune will take
care of them for you.
Solution
Reduce Pb
Increase Pb
Reduce Ti
Increase Ti
Reduce Td
Increase Td