O1TY
Output 1: Type of signal
O1FT
Output 1: Transfer mode in
event of failure.
Output 1: Hysteresis of
O1HY
output, in On/Off operation
only
CYC1
Output 1: Cycle time
OFST
Offset of proportional band
For offset correction
RAMP
Selection of ramp function
RR
Value of ramp
OUT2
Output 2: type of function
O2TY
Output 2: type of signal
0 rELY:
Relay output
1 SSrd:
Logic output for static relay
(20ms)
2 SSr: Logic output for static relay
3 4-20: Current output, 4-20mA
4 0-20: Current output, 0-20mA
5 0-1v: Voltage output, 0-1V
6 0-5v: Voltage output, 0-5V
7 1-5v: Voltage output, 1-5V
8 0-10: Voltage output, 0-10V
Select smooth transfer BPLS or 0.0 ∼ 100.0%
power on output 1, when the regulation loop
fails
BPLS OFF
BPLS ON
Min: 0.1 Max: 50.0° C
Min: 0.1 Max: 90.0 sec.
Min: 0 Max: 100.0%
0 nonE: No ramp function
1 mi n.r:
Use unit/minute for ramp speed
2 Hr.r: Use unit/hour for ramp speed
Min: 0
Max: 500° C
0 nonE: No function for output 2
1 tim.r: Timer
2 dE.Hi: Difference alarm, high
3 dE.Hi: Difference alarm, low
4 db.Hi: High symmetrical alarm
5 db.Lo: Low symmetrical alarm
6 Pu.Hi: High absolute alarm
7 Pu.Lo: Low absolute alarm
8 Cool: COLD regulation (with PID)
0 rELY:Output relay
1 SSrd: Logic output for static relay (20ms)
2 SSr: Logic output for static relay
3 4-20: Output current, 4-20mA
4 0-20: Output current, 0-20mA
5 0-1v: Output voltage, 0-1V
6 0-5v: Output voltage, 0-5V
7 1-5v: Output voltage, 1-5V
8 0-10: Output voltage, 0-10V
0
0
0.1
18.0
25.0
0
0.0
2
0
Page 42