Output 1
Output 2
ON-OFF
P or PD
PID
Cycle time
Manual command
Autotune
Fault mode:
malfunctions
Ramp speed:
Digital filter
First-order function
Time constant:
Environmental and physical characteristics
Operating temperature
Storage temperature
Humidity
Insulation resistance
Dielectric strength
Vibration resistance
Impact resistance
Moulded parts
Dimensions
STATOP 24.15 ----50 mm (L) X 26.5 mm (H) X 110.5 mm (D)
STATOP48.15 ----48 mm (L) X 48 mm (H) X 94 mm (D)
Mass
STATOP 24.15----- 120 g
STATOP 48.15----- 140 g
Standards
Safety
EMC
Reverse action for heating or direct action for cooling
Cooling command with PID
With adjustment of hysteresis
0 – 100.0% with adjustment of offset
Modified by fuzzy logic
Proportional zone 0.1 ∼ 500.0° C
Integral time
0 - 1,000 seconds
Derivative time
0 – 360.0 seconds
0.1 – 90.0 seconds
For heating (MV1) and cooling (MV2)
Cold start-up and hot start-up
Automatic transfer to manual mode if a sensor fails or the A/D converter
0 – 500.0° C / min.
0 – 500.0° C / hour
0, 0.2, 0.5, 1, 2, 5, 10, 20, 30, 60 seconds, programmable
-10° C to 50° C
- 40° C to 60° C
0 to 90% RH (without condensation)
20 M Ω min. (at 500 VDC)
2000 VAC, 50/60 Hz, for 1 minute
10 – 55 Hz, 10 m/s² for 2 hours
200 m/s² (20 g)
polycarbonate, non-inflammable
Depth behind panel 98 mm
Depth behind panel 86 mm
UL61010C-1
CSA C22.2 No. 24-93
EN61010-1 (IEC1010-1)
EN61326