Chauvin Arnoux PYROCONTROLE STATOP 15 Série Notice De Fonctionnement page 43

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

O2FT
Output 2: transfer mode in
event of failure
O2HY
Output 2: hysteresis in alarm
mode
CYC2
Output 2: cycle time
CPB
COLD: Value of proportional
band
DB
HOT/COLD Dead zone
(negative = overlap)
ALMD
Special alarms function
COMM
Communication
ADDR
Address of product
BAUD
Digital communication rate
DATA
Number of data bits
PARI
Parity bit
Select smooth transfer BPLS or 0.0 ∼ 100.0%
power on output 1 when regulation loop fails
BPLS OFF or BPLS ON
Min: 0.1
Max: 50.0° C
Min: 0.1 Max: 90.0° sec.
Min: 0.1
Max: 300%
Min: -36.0
Max: 36.0%
0 norm: Normal alarm
1 Ltch: Latching of state
2 HoLd: Disable 1st fault
3 Lt.Ho: Combined Ltch + Hold actions
0 nonE: No communication
1 rtu:
MODBUS – RTU protocol -
Min: 1 Max: 255
0
2,4:
2.4 Kbaud
1
4,8:
4.8 Kbaud
2
9,6:
9.6 Kbaud
3
14,4:
14.4 Kbaud
4
19,2:
19.2 Kbaud
5
28,8:
28.8 Kbaud
6
38,4:
38.4 Kbaud
0
7 bit:
7 data bits
1
8 bit:
8 data bits
0
Even:
Even parity
1
odd:
Odd parity
0
0.1°C
18.0
1000
0
0
1
1
2
1
0
Page 43