4 OPERATION

4.4.2 Span-compensation

The option to correct the basic adjustment of 20 mA. The procedure is identical to the Off-
set procedure. When ENTER is pressed while "SPAN" is indicated, the transmitter produces
20 mA. If this value is incorrect (within the limit of -1/+1 mA), it can be corrected by entering
the measured value.
ENTER
SPAN
ENTER
FREQUENC

4.4.3 Frequency display

Here, the sensor frequency is displayed until the Enter key is pressed.
ENTER
FREQUENC
ENTER
FLOW

4.4.4 Flow simulation

A flow can be simulated in this menu. This allows the user to test his system without any
liquid. Eventhough the simulated value influences the output current and the relays, it has
no impact on the pulse output. Unit and decimal place, as selected in the sub-menu "UNIT"
are active.
ENTER
FLOW
ENTER
FLOW
The simulation is active until the user enters into another sub-menu.
SP = 20.00
0......9
SP = 19.90
Entering the measured value
195.3 HZ
00.00L/S
Enter flow value
0......9
46.25L/S
E-22-
FLOW TRANSMITTER 8035