3 INSTALLATION

3.3 General Electrical Connection

The connecting line conducts the measuring signal and must not be installed in combination
with high voltage or high frequency carrying lines. If a combined installation cannot be
avoided, either keep a min. space of 30 cm (approx. 1 ft) or use coax cables. When using
coax cables observe faultless grounding of the shield. For normal operating conditions,
the measuring signal can be transmitted by a simple cable of 0.75 mm
Always use a coax cable in case of doubt.
The power supply must be of good quality (filtrated and regulated).
Note: For EMC purposes,the earth must be connected via the earth lug on the side
of the enclosure . This point must be connected locally to a good earth.

3.4. Electrical wiring

3.4.1 Connecting Transmitter SE35 without relay
Fig. 3.3 Cable plug assembly
1.
To open the connector remove screws 1.
2.
Remove internal part 3 from external part 2.
3.
Connect according to above pin assignment.
4.
When re-assembling, the internal part may be
inserted into the external part in 90 °-step intervals as
required.
8035
FLOW TRANSMITTER 8035
Wiring via cable plug
Standard DIN 43 650 plug connector with
PG9-cable glands, pipe cross section max.
2
1.5 mm
, IP65 rating (fig. 2). Open plug and
wire according following istructions:
1: L+ (12...30 VDC)
2: Pulse output A
y: Pulse output B
3: L-
Note: The pulse output of the Transmitter SE35
can easily be connected to a PLC.(fig. 3.5).