No.
Description
4.2.3.0
Countdown, pump
cycling
4.2.4.0
Remaining time
until pump kick
4.2.5.0
Mains on meter
4.2.6.0
Pump kick counter
4.3.0.0
States
4.3.1.0
Base-load pump
4.3.2.0
SSM
4.3.3.0
SBM
68
Type
Symbol Values/explanations
Time to pump cycling in h
(at a resolution of 0.1 h)
Time until the next pump kick
(after a pump has had a 24 h
standstill (e.g. via Ext. Off), it will
be automatically operated for
5 seconds)
Number of switching-on proce-
dures of the supply voltage
(each occasion the supply volt-
age is established after an inter-
ruption is counted)
Number of pump kicks carried
out
The value display statically
shows the identity of the regular
base-load pump.
The unit display statically shows
the identity of the temporary
regular base-load pump.
ON
State of the SSM relay
OFF
State of the SSM relay if no fault
signal is present
ON
State of the SBM relay if a readi-
ness/operation or mains on sig-
nal is present
OFF
State of the SBM relay if no
readiness/operation or mains
on signal is present
SBM
Run signal
Display conditions
Is only shown for DP-MA and
internal pump cycling
Is only displayed in DP-MA
mode