Operating Manual
• If the Orion G Multigas and Leak Detector was ordered with the
optional datalogging, the MSA FiveStar LINK software can be
used to set most of the instrument selections, including some
that cannot be changed from the instrument's front panel
buttons.
• See TABLE 4-4 for available selections and methods for
changing those selections.
Table 4-4. Available Instrument Selections and
Methods for Changing Selections
OPTION
Viewing alarm set-points
Changing alarm set-points
Changing Auto-Cal values
Setting Date/Time
Changing Time and Date (Datalog Equipped
Instruments Only)
To Change the Time of Day:
1. Push the ON-OFF/PAGE button until the Time page appears.
2. Push and hold the CHANGE/RESET button until the TIME
flag flashes.
3. Push the ON-OFF/PAGE button to change the time.
4. Push and hold the CHANGE/RESET button to advance
the hour.
5. When the correct hour displays, push the ON-OFF/PAGE
button once to advance to the Minutes page.
• The minutes should be flashing.
6. Press and hold the CHANGE/RESET button to advance
the minutes.
7. When the correct minute displays, push the ON-OFF/PAGE
button to leave the Time Set mode.
To Change the Date:
1. Push the ON-OFF/PAGE button until the Date page appears.
2. Push and hold the CHANGE/RESET button until the
MM/DD/YY flags flash.
Chapter 4, Setting up the Gas Utility Instrument
Orion G
FRONT-PANEL
BUTTONS
•
•
•
FIVESTAR LINK
•
•
•
4-5