Inputs
Power supply
Set value
Binary input,
valve adjustment the autotune function
Outputs
Instantaneous
value output
Relay output 1
Relay output 2
The controller is equipped with a serial interface that is used in the works for
communication during calibration. The interface may also be used to set up
communication with the service department of the manufacturer over the telephone
network via a special cable and Modem. In this way, for example, a rapid diagnosis
can be made in case of problems. You can obtain more details on this service option
via the contact address given in 1.2.
32
Specification
24 VDC ± 10%
Residual ripple 10%
4-20 mA (input resistance < 200 Ω)
0-10 V (input resistance > 500 kΩ)
0-5 V (input resistance > 500 kΩ)
Short-circuiting for approx. 1 s trips
Specification
4-20 mA (load resistance < 530 Ω)
0-10 V (max. current 20 mA)
0-5 V (max. current 20 mA)
potential-free make contact
(25VAC, 60VDC, 1 A)
is set when t
/t > 95% (see 2.4)
on
potential-free make contact
(25VAC, 60VDC, 1 A)
is set on sensor fault
Pins connected
-
Pins 1 (+)
+
und 6 (-)
Pins 1 (+)
und 2 (-)
2
- +
7 8
Pins 7 and 8
Pins connected
Pins 3 (+)
und 4 (-)
4 3
- +
Pins 2 und 5
Pins 3 and 7
Type 8626