Use the arrow until P2011 appears in the display. Press OK → in000 → press OK. Use the up arrow until the
display reads 1, press OK and press M.
•
Use the arrow until P2012 appears in the display. Press OK → in000 → press OK. Use the up arrow until the
display reads 8, press OK and press M.
•
Use the arrow until P2013 appears in the display. Press OK → in000 → press OK. Use the down arrow until the
display reads 4, press OK and press M.
•
Use the arrow until P1300 appears in the display. Press OK → in000 → press OK. Use the up arrow until the
display reads 0, press OK and press M.
•
Switch off the blower on the main switch, and wait at least ½ minute before switching it on again.
•
In case it is not possible to load the new data (for 4370, 4450 and 4550 with Siemens G120X converter), the
frequency converter is not set up to communicate to the PLC. If so, proceed as follows:
•
Check all cable connections according to the wiring diagram (if the LINK and Rx/Tx diodes are flashing, the
network cable between the PLC and the converter is OK).
•
Switch off the blower on the main switch.
•
Insert an SD card with software into the top of the converter (A).
•
Switch on the blower on the main switch.
•
The converter is now retrieving parameter data (B).
•
When the RDY LED turns green, switch off the blower on the main switch (C).
•
Remove the SD card.
•
Wait at least ½ minute before switching the blower back on.
A
Replacing the frequency converter
If the frequency converter has been replaced, proceed as follows:
•
login as Admin
•
press the Kongskilde logo in the upper right corner for 10 sec
•
The Kongskilde logo changes to LOAD MOTOR DATA and flashes
•
press the flashing LOAD MOTOR DATA
•
on the new page press: Load parameters to drive
•
when the blue bar is at 100%, press Return
The software is now downloaded to the frequency converter.
In the Supply Voltage field, you can change the parameters of the supply
voltage to the frequency converter, e.g. if the mains supply is 480V. This is
only necessary in case of repeated overvoltage faults when operating the
blower. See section "Troubleshooting" if necessary.
In the event that it is not possible to load the new data (for 4220 and 4300
Siemens V20 converter), the frequency converter is not set up to com-
municate to the PLC. If so, proceed as follows:
•
Check all cable connections according to the wiring diagram.
•
On the frequency converter, press M twice so that P0003 appears in
the display. Press OK and use the arrow until it reads 3 and finish with
OK.
•
Use the arrow until P2010 appears in the display. Press OK → in000
→ press OK. Use the up arrow until the display reads 8, press OK and
press M.
B
C