INSTALLATIoN AND TEST oF ThE SAFETy TEMPERATURE LIMITER STB
Installation of safety temperature limiter STB
Unreel the capillary of a safety temperature limiter STB and insert it into the sleeve on
boiler or system's heat source. It is important that the capillary has very good surface con-
tact with the sleeve wall.
Test of safety temperature limiter STB
Press and hold key
activates boiler or system's heat source and switches off all other outputs. Boiler is warm-
ing up on temperature 115 °C, i.e. to the temperature 110 ± 2 °C when the safety tempera-
ture limiter STB shall activate. Safety limiter test will automatically expire if safety limiter
has activated or if heat source temperature has exceeded 115 °C or in 20 minutes after the
test has been started. To stop safety limiter test at anytime press key
Activated safety temperature limiter is indicated with red illuminated ring around STB.
Activated safety temperature limiter needs to be reset before continuing with the system
operation. To reset it, wait for the heat source temperature to drop below 100 °C and then
press with appropriate tool into the hole of STB.
If safety temperature limiter fails to activate at 110 °C ± 2 °C, check if
thicker part of capillary has good contact with the sleeve wall or that capil-
lary tube isn't sharp bended or damaged. In other case the safety tempera-
ture limiter STB needs to be replaced.