General settings:
Para-
Parameter name
meter
P1.1
AUT. SWITCHOVER
SUMMER / WINTER
P1.2
AVERAGE OUTDOOR
TEMP. FOR SUMMER /
WINTER SWITCHOVER
P1.3
OUTDOOR TEMP. FOR
ACTIVATION OF FROST
PROTECTION
P1.4
REQUESTED ROOM
TEMP. WHEN HEATING IS
SWITCHED OFF
P1.5
TEMPERATURE ROUND
UP
P1.6
AUT. SHIFT OF CLOCK
TO SUMMER / WINTER
TIME
P1.7
PERIOD OF TEMPERAT.
LOGGING
P1.8
TONES
P1.9
ADVANCED DISPLAY OF
TEMPERATURES
P1.10
LEVEL OF PROTECTION
AGAINST FROST
Service setting manual
Parameter description
Automatic switch-off and switch-on of heating in respect to
average one-day outdoor temperature.
Setting of average one-day outdoor temperature at which
the heating should switch-off or switch-on.
Setting of outdoor temperature by which the frost protec-
tion will activate and run boiler at minimum temperature.
Setting of requested room temperature when heating is
switched off.
Precision of displayed temperatures.
With the help of a calendar, the controller carries out the
automatic clock changeover between summer and winter
time.
By setting this field you define how often the measured
temperatures are saved.
By setting this field you define whether key pressing is
accompanied with sound signals or not.
Advanced display of temperatures displays temperatures
on main screen in double rows. First row is measured
temperature; second row is required or calculated
temperature.
With this setting, we determine the level of protection
against frost that depends on the assessment of the
possibilities for frost on the facility.
Choose 0 level, when there is no possibility of frost on
the facility.
Choose 1 level, when there is a possibility of frost on the
facility. If room temperature sensor isn't connected, hea-
ting system parts that are particularly exposed to freezing
are protected, when heating is switched off.
Choose 2 level, when there is a possibility of frost on the
facility. Heating system parts that are particularly exposed
to freezing are protected, when heating is switched off.
Choose level 3, when the possibility of frost on the facility
is considerable and parts of the heating system are
particularly exposed to freezing.
36
Setting range
Default
setting
0- NO
1
1- YES
10 ÷ 30 °C
18
-30 ÷ 10 °C
2
2 ÷ 12 °C
6
0- 0.1 °C
1- 0.2 °C
2
2- 0.5 °C
3- 1 °C
0- NO
1- YES
1
1 ÷ 30 min
5
0- OFF
1- KEYPAD
2- ERRORS
1
3- KEYPAD &
ERRORS
0- NO
1- YES
1
0 – NO PRO-
TECTION
1 - LEVEL 1
2 - LEVEL 2
3 - LEVEL 3
(GREATEST
PROTECTION)
1