Télécharger Imprimer la page

OEG KSF-Pro Mode D'emploi page 38

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Para-
Parameter name
meter
P4.2
PRIORITY OF D. H. W.
WARMING TO CIRCUIT 1
P4.3
PRIORITY OF D. H. W.
WARMING TO CIRCUIT 2
P4.7
TIME PROGRAM FOR D.
H. W. CIRCULATION
P4.8
RUNNING TIME FOR
D. H. W. CIRCULATION
PUMP
STAND-BY TIME FOR
P4.9
D. H. W. CIRCULATION
PUMP
Settings for boilers:
Para-
Parameter name
meter
P5.1
MIN. LIQUID FUEL
BOILER TEMP.
P5.2
MIN. SOLID FUEL
BOILER TEMP.
P5.3
MIN. HEAT ACCUMULA-
TOR TEMP.
P5.5
CONSUMPTION OF
LIQUID FUEL BOILER -
BURNER STAGE 1
P5.6
CONSUMPTION OF
LIQUID FUEL BOILER -
BURNER STAGE 2
P5.7
ENERGY SOURCE IN
LIQUID FUEL BOILER
Settings for alternative energy sources:
Para-
Parameter name
meter
P6.1
SWITCH-ON DIFFE-
RENCE FOR COLLEC-
TORS OR SOLID FUEL
BOILER
Service setting manual
Parameter description
Setting if d. h. w. heating has priority to room heating in
circuit 1.
Setting if d. h. w. heating has priority to room heating in
circuit 2.
Selection of d. h. w. warming time program which will be
used for d. h. w. circulation.
Setting 1 is first time program for domestic hot water
warming.
Setting 2 is second time program for domestic hot eater
warming.
Setting 3 is selected time program for domestic hot water
warming.
Setting of running time for d. h. w. circulation pump. Pump
running period is always followed by the pump stand-by
period.
Setting of stand-by time for d. h. w. circulation pump.
Pump stand-by period is always followed by the pump
running period.
Parameter description
Setting of min. liquid fuel boiler temperature.
Setting of min. solid fuel boiler temperature.
Setting of min. temperature for heat transfer from storage
tank.
Setting of liquid fuel boiler consumption on 1st stage of the
burner (Unit: L/h for heating oil or Sm3/h for natural gas).
Setting of liquid fuel boiler consumption on 2nd stage of the
burner (Unit: L/h for heating oil or Sm3/h for natural gas).
Selection of energy source used to fire liquid fuel boiler.
Parameter description
Setting of difference between solar collectors or solid fuel
boiler temperature and storage tank or heat accumulator
temperature by which the circulation pump shall switch-on.
38
Setting range
Default
setting
0- NO
1- YES
0
0- NO
1- YES
0
1- PROG. 1
2- PROG. 2
3- SELECT.
PROG.
3
0 ÷ 600 sec
300
0 ÷ 60 min
10
Setting
Default
range
setting
10 ÷ 90 °C
35
10 ÷ 90 °C
55
20 ÷ 70 °C
30
0.0 ÷ 10.0
0.0
0.0 ÷ 10.0
0.0
1- HEATING
OIL
1
2- NATURAL
GAS
Setting
Default
range
setting
5 ÷ 30 °C
12