Electrical Connections - Crowcon Xgard IR Instructions D'installation, D'utilisation Et D'entretien

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 29
Xgard IR

2.4 Electrical connections

All connections are made via the screw terminal block mounted on the PCB in the
junction box. The terminals are marked '+', 'sig' and '-' and correct polarity should be
observed when connecting the detector to control equipment. Xgard IR is factory set
as a 'current sink' device unless otherwise specified when ordering. To reset to 'current
source', open the junction box and move the two links on the amplifier PCB from the
'sink position to the 'srce' position, as shown in Diagram 4.
Note: The internal grounding terminal (see diagram 4) shall be used as the grounding
means of the Xgard IR gas detector. The external grounding terminal is only to be used
where local authorities permit or require such a connection. Where possible, to limit
radio frequency interference, the junction box and cable armour should be grounded at
the control panel (safe area) only to avoid earth loops.
Xgard IR PCB
Diagram 5: Xgard IR electrical connections
-VE
SIG
+VE
Control panel
-VE
1
2
3
4
SIG
+VE
Earth
10-30 V cc
4-20 mA
(Sink or Source)
2.Installation
5
6
7
8
9
10
11
12
15

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

M07692

Table des Matières