MOTOR CONTROL
SLEW RATE LIMIT
–
TRUE – [ 60] ENABLE
500.0Hz/s – [ 62] ACCEL LIMIT
–
500.0Hz/s – [ 61] DECEL LIMIT
–
CALC NO LOAD I – [689] MODE
SLIP COMP
FALSE – [ 82] ENABLE
–
1420 n/min – [ 83] NAMEPLATE RPM
–
4 – [ 84] MOTOR POLES
–
120.0 n/min – [ 85] MOTORING LIMIT
–
120.0 n/min – [ 86] REGEN LIMIT
–
CURRENT FEEDBACK
MOTOR CURRENT [ 66] – 0.00%
MOTOR CURRENT [ 67] – 0.0A
I MAGNETISING [ 68] – 0.00%
I MAGNETISING [ 69] – 0.0A
I TORQUE [ 70] – 0.00%
I TORQUE [ 71] – 0.0A
LOAD [ 72] – 0.00%
FIELD [ 73] – 0.00%
** 3.4A – [ 64] FULL LOAD CALIB
–
** 1.9A – [ 65] NO LOAD CALIB
–
0.80 – [242] POWER FACTOR
–
CURRENT LIMIT
LIMITING [370] – FALSE
100.00% – [365] MOTOR I LIMIT
–
-100.00% – [623] REGEN I LIMIT
–
CURRENT – [366] FEEDBACK SOURCE –
TRUE – [686] REGEN LIM ENABLE –
STABILISATION
TRUE – [ 82] ENABLE
–
FLUXING
LINEAR LAW – [104] V/F SHAPE
–
100.00% – [105] V/F SCALE
–
* 50.0Hz – [106] BASE FREQUENCY –
120Hz – [113] LIMIT FREQUENCY –
6.00% – [107] FIXED BOOST
–
0.00% – [108] AUTO BOOST
–
VECTOR FLUXING
SUPPLY VOLTAGE [596] – 0.0V
BIDIRECTIONAL – [572] SEARCH MODE
–
FALSE – [118] ENABLE
** DELTA – [124] MOTOR CONNECTION –
** 1.00 Ohm – [119] STATOR RES
–
** 10.0mH – [120] LEAKAGE INDUC
–
** 1000.0mH – [121] MUTUAL INDUC
–
605 Series Frequency Inverter - HA463544
AUTOTUNE
ACTIVE [604] –FALSE
FALSE – [603] ENABLE
–
–
VOLTAGE CONTROL
[595] VOLTAGE MODE
–
NONE
** 230.0V – [122] MOTOR VOLTS
–
100.00% – [112] BASE VOLTS
–
UNDERLAP COMP
TRUE – [600] ENABLE
–
PATTERN GEN
DRIVE FREQUENCY [591] – 0.0Hz
VOLTS [592] – 0.0V
BOOST [593] – 0.0V
TRUE – [ 98] RANDOM PATTERN
–
3kHz – [ 99] FREQ SELECT
–
2.0s – [100] DEFLUX DELAY
–
DYNAMIC BRAKING
DC LINK VOLTS [ 75] – 0.0V
BRAKING [ 81] – FALSE
TRUE – [ 80] ENABLE
–
100 Ohm – [ 77] BRAKE RESISTANCE –
PROP. W/MIN. – [338] MODE
0.1kW – [ 78] BRAKE POWER
–
25 – [ 79] 1 SEC OVER RATING –
INJ BRAKING
ACTIVE [583] – FALSE
0.5s – [710] DEFLUX TIME
–
9.0Hz – [577] FREQUENCY
–
100.00% – [578] I-LIM LEVEL
–
2.0s – [579] DC PULSE
–
1.0s – [580] FINAL DC PULSE
–
5.00% – [581] DC LEVEL
–
600.0s – [582] TIMEOUT
–
FLYCATCHING
ACTIVE
[576] –FALSE
SETPOINT
[ 28] –0.00%
FALSE – [570] ENABLE
–
ALWAYS – [571] START MODE
–
–
9.00% – [573] SEARCH VOLTS
–
35.00% – [ 32] SEARCH BOOST
–
5.0s – [574] SEARCH TIME
–
5.0Hz – [575] MIN SEARCH SPEED –
3.0s – [709] REFLUX TIME
–
SETPOINT FUNCS
RAISE/LOWER
OUTPUT [325] – 0.00%
FALSE – [327] RAISE INPUT
–
FALSE – [328] LOWER INPUT
–
10.0s – [326] RAMP RATE
–
100.00% – [330] MAX VALUE
–
-100.00% – [329] MIN VALUE
–
0.00% – [331] RESET VALUE
–
FALSE – [332] RESET
–
SKIP FREQUENCIES
OUTPUT [346] – 0.0%
OUTPUT Hz [363] – 0.0Hz
INPUT Hz [362] – 0.0Hz
0.00% – [340] INPUT
–
0.0Hz – [341] BAND1
–
0.0Hz – [342] FREQUENCY 1
–
0.0Hz – [680] BAND 2
–
0.0Hz – [343] FREQUENCY 2
–
0.0Hz – [681] BAND 3
–
0.0Hz – [344] FREQUENCY 3
–
0.0Hz – [682] BAND4
–
0.0Hz – [345] FREQUENCY 4
–
MINIMUM SPEED
OUTPUT [335] – 0.00%
–
0.00% – [336] INPUT
-100.00% – [337] MINIMUM
–
–
PID
PID OUTPUT [320] – 0.00%
0.00% – [310] ERROR INPUT
–
FALSE – [311] ENABLE
–
FALSE – [312] INTEGRAL DEFEAT –
1.0 – [313] P GAIN
–
1.00s – [314] I TIME CONST
–
TERMINALS/COMMS – [307] REMOTE SEQ MODES –
0.000s – [315] D TIME CONST
–
TERMINALS/COMMS – [308] REMOTE REF MODES –
2.000s – [316] FILTER TC
–
100.00% – [317] OUTPUT POS LIMIT –
-100.00% – [318] OUTPUT NEG LIMIT –
1.0000% – [319] OUTPUT SCALING –
BRAKE CONTROL
RELEASE [587] – FALSE
HOLD [590] – FALSE
50.00% – [584] ON LOAD
–
5.0Hz – [585] ON FREQUENCY
–
3.0Hz – [586] OFF FREQUENCY
–
0.00s – [588] ON HOLD TIME
–
0.00s – [589] OFF HOLD TIME
–
145
SEQ & REF
AUTO RESTART
PENDING [608] – FALSE
RESTARTING [616] – FALSE
ATTEMPTS LEFT [614] – 5
TIME LEFT [615] – 10.0s
FALSE – [611] ENABLE
–
5 – [612] ATTEMPTS
–
10.0s – [610] INITIAL DELAY 1
–
10.0s – [613] ATTEMPT DELAY 1
–
0000 – [609] TRIGGERS 1
–
0.1s – [678] INITIAL DELAY 2
–
0.1s – [679] ATTEMPT DELAY 2
–
0000 – [677] TRIGGERS 2
–
LOCAL CONTROL
REMOTE SEQ
[297] –TRUE
REMOTE REF
[257] –TRUE
LOCAL/REMOTE – [298] SEQ MODES
–
LOCAL/REMOTE – [265] REF MODES
–
REMOTE – [299] POWER UP MODE –
FALSE – [281] SEQ DIRECTION
–
SERIAL LINKS
COMMS CONTROL
COMMS SEQ [295] – FALSE
COMMS REF [270] – FALSE
COMMS STATUS [272] – 0000
COMMS COMMAND [273] – 0000
FALSE – [300] REMOTE COMMS SEL –
0.0s – [309] COMMS TIMEOUT
–
SYSTEM PORT (P3)
0 – [102] GROUP ID (GID)
–
0 – [103] UNIT ID (UID)
–
16
Application Macros
MENUS
OP STATION
OP DATABASE [115] –FALSE
OP VERSION [230] –0000
BASIC – [ 3]
VIEW LEVEL
–
* ENGLISH – [ 1]
LANGUAGE
–
00F0 – [127] ENABLED KEYS
–
FALSE – [116] AUTO BACKUP
–
* AC MOTOR DRIVE – [339] CONFIGURATION ID –
PASSWORD
–
0000
[ 7]
ENTER PASSWORD
–
0000
[ 8]
CHANGE PASSWORD
FALSE – [361] PROTECT LOCAL SP
–
FALSE – [364] PROTECT OP MENU
–
OPERATOR MENU
1 – [93] STARTUP SCREEN
–
255 – [626] OPERATOR MENU 2
–
591 – [627] OPERATOR MENU 3
–
67 – [628] OPERATOR MENU 4
–
72 – [629] OPERATOR MENU 5
–
75 – [630] OPERATOR MENU 6
–
370 – [631] OPERATOR MENU 7
–
0 – [632] OPERATOR MENU 8
–
0 – [633] OPERATOR MENU 9
–
0 – [634] OPERATOR MENU 10 –
0 – [635] OPERATOR MENU 11 –
0 – [636] OPERATOR MENU 12 –
0 – [637] OPERATOR MENU 13 –
0 – [638] OPERATOR MENU 14 –
0 – [639] OPERATOR MENU 15 –
CUSTOM SCREEN 1
0 – [ 74] TAG NO
–
– [324] NAME
–
– [323] UNITS
–
xxxxx. – [334] DECIMAL PLACE
–
A/B * X + C – [125] FORMULA
–
100 – [321] COEFFICIENT A
–
100 – [ 44] COEFFICIENT B
–
0 – [322] COEFFICIENT C
–
30000 – [101] HIGH LIMIT
–
-30000 – [ 53] LOW LIMIT
–
CUSTOM SCREEN 2
0 – [371] TAG NO
–
– [378] NAME
–
– [377] UNITS
–
xxxxx. – [379] DECIMAL PLACE
–
A/B * X + C – [676] FORMULA
–
100 – [375] COEFFICIENT A
–
100 – [673] COEFFICIENT B
–
0 – [376] COEFFICIENT C
–
30000 – [674] HIGH LIMIT
–
-30000 – [675] LOW LIMIT
–
Macro 0