No.
Designation
4.2.1.0
Operating hours
4.2.2.0
Consumption
4.2.3.0
Countdown, pump
cycling
4.2.4.0
Remaining time
until pump kick
4.2.5.0
Mains On counter
4.2.6.0
Pump kick counter
4.3.0.0
States
4.3.1.0
Base-load pump
4.3.2.0
SSM
4.3.3.0
SBM
Installation and operating instructions Wilo-VeroLine IP-E, Wilo-VeroTwin DP-E
Type
Symbol Values/explanations
Sum of the pump's active hours
of operation
(meter can be reset by infrared
interface)
Energy consumption
in kWh/MWh
Time to pump cycling in h
(at a resolution of 0.1 h)
Time until the next pump kick
(after a pump has had a 24 h
standstill (e.g. via Ext. Off), it will
be automatically operated for
5 seconds)
Number of switching-on proce-
dures of the supply voltage
(each occasion the supply
voltage is established after an
interruption is counted)
Number of pump kicks that have
occurred
The value display statically
shows the identity of the regular
base-load pump.
The unit display statically shows
the identity of the temporary
regular base-load pump.
ON
State of the SSM relay if there is
no fault signal
OFF
State of the SSM relay if no fault
signal is present
ON
State of the SBM relay if a readi-
ness/operation or mains On sig-
nal is present
OFF
State of the SBM relay if no read-
iness/operation or mains On sig-
nal is present
English
Display conditions
Shown only for DP-MA and
internal pump cycling Can be
set in the service menu
<5.1.3.0>
Only displayed in DP-MA
mode
75