Operation; Operating Elements - salmson SIE Installation Et Mise En Service

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
Differential pressure sensor
connection
Procedure
8

Operation

8.1

Operating elements

The red button
Fig. 24: The red button
DIP switch
1 2 3 4
Fig. 25: DIP switch
Installation and operating instructions SIE-DIE-PBE
NOTE
The terminals In1, In2, AUX, GND, Ext. off and MP meet the require-
ment for "safe isolation" (in acc. with EN 61800-5-1) to the mains
terminals, as well as to the SBM and SSM terminals (and vice versa).
NOTE
The control is designed as a PELV (protective extra low voltage) cir-
cuit, meaning that the (internal) supply meets the requirements for
safe supply isolation; the GND is connected to PE.
Cable
1
2
3
NOTE
The electrical connection of the differential pressure sensor is to be
fed through the smallest threaded cable connection (M12) on the
module.
• Establish connections observing the terminal allocation.
• Earth the pump/installation in accordance with regulations.
The electronics module is operated using the following operating ele-
ments:
The red button (Fig. 24) can be turned to select menu elements and
used to change values. Pressing the red button activates a selected
menu element and confirms values.
ON
The DIP switches (Fig. 8, Item 6/Fig. 25) are located under the housing
cover.
• Switch 1 is for switching between the standard and service mode.
For additional information, see Section 8.6.6 "Activating/deactivating
service mode" on page 82.
• Switch 2 allows activation or deactivation of the access disable fea-
ture.
For additional information, see Section 8.6.7 "Activating/deactivating
access disable" on page 82.
• Switches 3 and 4 permit termination of the multi-pump communica-
tion.
For additional information, see Section 8.6.8 "Activating/deactivating
termination" on page 82.
Colour
Terminal
black
IN1
blue
GND
brown
+24 V
English
Function
Signal
Earth
+24 V
75

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

DiePbeSie serieDie serieSie 2 04-17/5,5Die 2 04-17/5,5

Table des Matières