5

Product information

5.1

Type key

5.2

Technical data

Property
Speed
Nominal diameters DN
Pipe connections
Approved fluids
Permissible min./max. fluid temperature
Ambient temperature min./max.
Max. admissible operating pressure
Sound pressure level
Insulation class
Protection class
Electromagnetic compatibility*)
Emitted interference in acc. with
Interference resistance in acc. with
Electrical connection
Internal electric circuit
Speed control
Relative humidity
*) Pumps with motor power between 11 kW and 22 kW can cause radio interference in residential spaces; should this be the case it may be necessary for the
operator to implement appropriate measures.
Fluids
Installation and operating instructions SIE-DIE-PBE
The type key consists of the following elements:
Example:
SIE 2 04-17/5,5
DIE 2 04-17/5,5
PBE 2 04-17/5,5
SI
Flange-end pump as inline single pump
DI
Flange-end pump as inline double pump
PB
Flange-end pump as monobloc pump
E
With Electric module for electronic speed control
2
2 poles motor
04
Nominal diameter of flanges
17
Nominal diameter of impellers
5,5
Motor power in kW
Value
750 - 2900 rpm; 380 - 1450 rpm
SIE/DIE:
40, 50, 65, 80, 100, 125,
150, 200 mm
PBE:
32, 40, 50, 65, 80, 100,
125 mm (pressure side)
Flanges PN 16
Heating water according to VDI 2035
Cooling/cold water
Water/glycol mixture up to 40 % vol.
Heat transfer oil
Other fluids on request
-20 °C to +140 °C
0 °C to +40 °C
16 bar (120 °C)
13 bar (140 °C)
< 83 dB(A)
F
55
EN 61800-3
EN 61800-3
3~440 V ± 10 %, 50/60 Hz
3~400 V ± 10 %, 50/60 Hz
3~380 V -5 % + 10 %, 50/60 Hz
PELV, galvanically isolated
Built-in frequency converter
< 90 %, non-condensing
When ordering spare parts be sure to state all the information given
on the pump and motor type plates.
If water/glycol mixtures are used (or fluids with a viscosity other than
that of pure water), an increase in power consumption of the pump is
to be taken into account. Only use mixtures with corrosion inhibitors.
The respective manufacturer's instructions are to be observed.
• The fluid must be sediment-free.
• Salmson's approval must be obtained for use of other media.
English
Remarks
EN 1092-2
Standard version
Standard version
Standard version
Only for special version
Only for special version
Depending on fluid
Lower or higher ambient
temperature on request
Depending on pump type
Residential
Industrial
Supported network types:
TN, TT
59

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

DiePbeSie serieDie serieSie 2 04-17/5,5Die 2 04-17/5,5

Table des Matières