• Check the current type and voltage of the mains connection.
• Observe the type plate information for the pump. The current type
and voltage of the mains connection must correspond to the specifi-
cations on the name plate.
• Mains side fuse protection: max. permitted see following table;
Comply with the data on the rating plate.
1,5 - 4
max. fuse / A
25
• Take additional earthing into account!
• The use of a miniature circuit breaker is recommended.
NOTE
Miniature circuit breaker tripping characteristic: B
• Overload: 1.13-1.45 x I
nominal
• Short circuit: 3-5 x I
nominal
• Control terminal (Fig. 21)
(See following table for assignment)
Power P
/ kW:
N
5,5 - 11
15
18,5 - 22
25
35
50