10.6
Inspection
10.6.1
Pressure-bearing components
Comply with all applicable national regulations for the operation of pressure
equipment. De-pressurise all pressurised components prior to inspection (see
disassembly information).
10.6.2
Inspection prior to commissioning
In Germany, follow the Industrial Safety Regulation
[Betriebssicherheitsverordnung] Section 15 and Section 15 (3) in particular.
10.6.3
Inspection intervals
Recommended maximum inspection intervals for operation in Germany
pursuant to Section 16 of the Industrial Safety Regulation
[Betriebssicherheitsverordnung] and the vessel classification of the device in
diagram 2 of the Directive 2014/68/EC, applicable in strict compliance with the
Reflex Installation, Operation and Maintenance Manual.
External inspection:
No requirement according to Annex 2, Section 4, 5.8.
Internal inspection:
Maximum interval according to Annex 2, Section 4, 5 and 6; if necessary, suitable
replacement actions are to be taken (such as wall thickness measurement and
comparison with the design specification which may be requested from the
manufacturer).
Strength test:
Maximum interval according to Annex 2, Section 4, 5 and 6.
Furthermore, compliance with Section 16 of the Industrial Safety Regulation and
Section 16 (1) in particular, in conjunction with Annex 2, Section 4, 6.6 and
Annex 2, Section 4, 5.8, must be ensured.
The actual intervals must be specified by the operating company based on a
safety evaluation taking into consideration the actual operating conditions,
experience with the mode of operation and charging material and the applicable
national regulations for the operation of pressure equipment.
11
Disassembly
DANGER
Risk of serious injury or death due to electric shock.
If live parts are touched, there is risk of life-threatening injuries.
•
Ensure that the system is voltage-free before installing the device.
•
Ensure that the system is secured and cannot be reactivated by other
persons.
•
Ensure that installation work for the electric connection of the device is
carried out by an electrician, and in compliance with electrical engineering
regulations.
CAUTION
Risk of burns
Escaping hot medium can cause burns.
•
Maintain a sufficient distance from the escaping medium.
•
Wear suitable personal protective equipment (safety gloves and goggles).
CAUTION
Risk of burns on hot surfaces
Hot surfaces in heating systems can cause burns to the skin.
•
Wear protective gloves.
•
Please place appropriate warning signs in the vicinity of the device.
CAUTION
Risk of injury due to pressurised liquid
If installation or maintenance work is not carried out correctly, there is a risk of
burns and other injuries at the connection points, if pressurised hot water or
steam suddenly escapes.
•
Ensure proper disassembly.
•
Ensure that the system is de-pressurised before performing the
disassembly.
Prior to the disassembly, lock out the "DC" degassing lines and the "WC" make-
up line from the system to the Servimat and de-pressurise the Servimat. Then
disconnect the Servimat from all voltages.
Proceed as follows:
1.
Switch the system to stop mode and secure it to prevent it being switched
back on.
2.
Lock out the "DC" degassing lines and the "WC" make-up line.
3.
Switch the system to a voltage-free state. Unplug the Servimat's mains
plug from the power supply.
4.
Disconnect all cables from the terminals of the Servimat controller.
parts of the Servimat's circuit board may still be live with 230 V even after
the device has been physically isolated from the power supply by pulling
out of the mains plug. Before you remove the covers, completely isolate
the Servimat controller from the power supply. Verify that the main circuit
board is voltage-free.
5.
Open the "FD" drain cock at the "VT" spray tube of the Servimat until the
spray tube no longer contains any water.
6.
If necessary, physically remove the Servimat from the system.
The dismantling process is completed.
12
Annex
12.1
Reflex Customer Service
Central customer service
Central telephone number: +49 (0)2382 7069 - 0
Customer Service extension: +49 (0)2382 7069 - 9505
Fax: +49 (0)2382 7069 - 9523
E-mail: service@reflex.de
Technical Hotline
For questions about our products
Telephone number: +49 (0)2382 7069-9546
Monday to Friday 8:00 to 16:30
12.2
Conformity and standards
Device conformity declarations are available on the Reflex homepage.
www.reflex-winkelmann.com/konformitaetserklaerungen
Alternatively, scan the QR code:
12.3
Guarantee
The respective statutory guarantee regulations apply.
Servimat M/L — 28.01.2021
DANGER – Risk of serious injury or death due to electric shock. Some
Disassembly
English — 25