Controller
9.3.4
Degassing programmes – overview
i
You can choose between 2 degassing programs:
Continuous degassing
•
Usage:
–
For device commissioning.
–
For degassing of the water after a device or facility system repair.
•
Activation:
–
An automatic activation occurs after completion of the start routine
during initial commissioning.
•
Times:
–
The time can be set in the Customer menu.
–
The default setting is 24 hours. Subsequently, the system
automatically switches to Interval degassing.
In continuous degassing, the degassing cycles are sequentially performed for 24
hours.
Continuous degassing is pre-set in the customer menu as the default setting.
Interval degassing
•
Usage:
–
For continuous operation of the device.
•
Activation:
–
Automatic activation occurs after the ending of continuous
degassing.
•
Times:
–
8 degassing cycles per interval is set in the Service menu.
–
After 8 intervals there is an idling time of 24 hours.
–
The times for interval degassing are stored in the Service menu.
–
Daily start of interval degassing is at 8:00 a.m.
Note!
Manual activation of the degassing program takes place in the customer
menu.
9.3.5
Setting degassing programmes
1.
Press "Settings".
–
The controller switches to the setting area.
2.
Press "Customer >".
–
The controller opens the Customer menu.
3.
Press "Degassing >".
–
The controller switches to the selected area.
–
Use the scroll bar to navigate through the list.
20 — English
4.
Press "(012) Degassing programme".
–
The controller opens the list of degassing programmes.
5.
Press the desired button.
–
–
Confirm your selection with "OK".
–
Degassing is deactivated.
6.
Press "(013) Time, continuous degassing".
7.
Set the time for continuous degassing.
–
Use the "Left" and "Right" buttons to select the display value.
–
Use the "Up" and "Down" buttons to change the display value.
–
Confirm your entries with "OK".
Press "i" to display a help text for the selected area.
Press "X" to cancel your input without saving the new settings. The
controller automatically opens again the list.
Servimat M/L — 28.01.2021
"Continuous degassing" is selected in this example.
No degassing and interval degassing are deselected.