Controller
ER Code
Alarm
08
Pressure measurement
09
Level sensor
10
Maximum pressure
11
Make-up quantity
14
Discharge period
15
Make-up valve
16
Power failure
18
Parameter
19
Stop ˃ 4 hours
20
Max. Make-up volume
21
Maintenance recommended
24
Replace cartridge
25
Datalogger
30
I/O module fault
31
EEPROM defective
32
Undervoltage
33
Adjustment parameter
faulty
34
Communication
Main board faulty
35
Digital input voltage faulty
36
Analogue input voltage faulty
37
No MKH 1 input voltage
38
No MKH 2 input voltage
39
Pressure jumper
40
Level jumper
41
Replace battery
42
Bus module
22 — English
Floating
Causes
contact
YES
Controller receives incorrect
signal.
YES
Controller receives incorrect
signal.
-
Set value exceeded.
Pressure relief pipe not
functioning.
Dirt trap clogged.
-
"With water meter" must be activated
in the Customer menu.
Set value exceeded.
Severe water loss in the system.
-
Set value exceeded.
Degassing pipe closed.
Dirt trap clogged.
-
Contact water meter measures
without make-up requirement.
-
No power.
-
Parameter settings incorrect.
-
Device is in Stop mode for more
than 4 hours.
-
Set value exceeded.
-
Set value exceeded.
-
Set value for soft water capacity
exceeded.
-
No SD card inserted.
SD card write protected.
SD card not recognised.
-
I/O module defective.
Connection between option card
and controller faulty.
Option card defective.
YES
EEPROM defective.
Internal calculation error.
YES
Supply voltage too low.
YES
EPROM parameter memory
defective.
-
Connecting cable defective.
Main board defective.
-
Short-circuit of input voltage.
-
Short-circuit of input voltage.
-
Short-circuit of input voltage.
-
Short-circuit of input voltage.
-
Jumper J1 on the main board set
incorrectly.
-
Jumper J1 on the main board set
incorrectly.
-
Buffer battery discharged.
-
Bus module activated but not
present.
Connecting cable defective.
Bus module defective.
Servimat M/L — 28.01.2021
Remedy
Connect the plug.
Check functioning of the pressure
sensor.
Check the cable for damage.
Check the pressure sensor.
Check functioning of the load cell.
Check the cable for damage.
Connect the plug.
Check set value in the Customer or
Service menu.
Check functioning of the pressure relief
pipe.
Clean the dirt trap.
Check set value in the Customer or
Service menu.
Check water loss in the system and
repair, if necessary.
Check degassing line.
Check dirt trap.
Check the make-up valve for leaks.
Connect to power supply.
Check settings, if necessary make basic
settings in the service menu.
Set the controller to Automatic mode.
Reset the "Make-up quantity" meter in
the Customer menu.
Perform maintenance and reset the
maintenance counter upon completion.
Replace cartridges.
Set soft water capacity.
Insert FAT16 or FAT32 formatted SD
card.
Disable write-protection.
Check SD card.
Inform Reflex Customer Service.
Inform Reflex Customer Service.
Check power supply.
Inform Reflex Customer Service.
Inform Reflex Customer Service.
Check the wiring at the digital inputs
(water meter, for example).
Check the wiring at the analogue inputs
(pressure/level).
Check wiring of the ball valve.
Check wiring of the ball valve.
Change the jumper setting accordingly.
Change the jumper setting accordingly.
Replace the battery in the operating
unit (CPU).
Connect bus module.
Check connection cable.
Replace bus module.
Alarm reset
"Quit"
"Quit"
"Quit"
"Quit"
"Quit"
-
-
"Quit"
"Quit"
"Quit"
-
-
"Quit"
-
-
-
-
-
-
-