Controller
4.
Select the calculated minimum operating pressure and conform your entry
with "OK".
For calculating the minimum operating pressure, see chapter 7.2
"Determining the P
minimum operating pressure for the controller"
0
on page 13 .
5.
Set the time.
Use the "Left" and "Right" buttons to select the display value.
Use the "Up" and "Down" buttons to change the display value.
Confirm your entries with "OK".
The time of an alarm will be stored in the fault memory of the
controller.
6.
Set the date.
Use the "Left" and "Right" buttons to select the display value.
Use the "Up" and "Down" buttons to change the display value.
Confirm your entries with "OK".
The date of an alarm will be stored in the fault memory of the
controller.
7.
Select the size of the primary tank.
Use the "Up" and "Down" buttons to change the display value.
Confirm your entries with "OK".
For the primary tank data, see the name plate or see chapter 5
"Technical data" on page 6 .
18 — English
The controller checks whether the level measuring signal matches
the dimensional data of the primary tank. The primary tank must be
fully emptied, see see chapter 6.3.6 "Fitting the level sensor" on
page 10 .
8.
Press "OK".
Null balancing is executed.
If null balancing is not successfully completed, you cannot
commission the device. In this case, please contact Customer Service,
see chapter 12.1 "Reflex Customer Service" on page 25
9.
Once null balancing has concluded successfully, you can end the start
routine by pressing the "OK" button.

Note!
After successful conclusion of the start routine, you are in Stop mode. Do
not yet switch to Automatic mode.
9.3.1

Customer menu

9.3.1.1
Customer menu – overview
Use the Customer menu to correct or determine system-specific values. In the
course of initial commissioning, the factory settings must be adjusted for the
system-specific conditions.

Note!
For a description of the operation, see chapter 9.1 "Operator panel" on
page 17 .
A three-digit PM code is assigned to the setting options
PM code
Description
001
Select the language
002
Set the time
003
Set the date
Execute null balancing
005
Set the P
"Determining the P
on page 13 .
Degassing >
012
013
Make-up >
023
024
027
028
Servimat M/L — 28.01.2021
The primary tank must be empty
The system checks whether the signal from the level sensor
matches the selected primary tank.
minimum operating pressure, see chapter 7.2
0
minimum operating pressure for the controller"
0
Degassing programme
No degassing
Continuous degassing
Interval degassing
Continuous degassing time
Maximum make-up time ...min
Maximum make-up cycles ... /2 h
With water meter "Yes/'No"
If "Yes", continue with 028
If "No", continue with 007
Make-up quantity (Reset) "Yes/No"
If "Yes", reset to "0"