6.1 PROCESS CHARACTERISTICS
Flow measurement
- Type of measurement
- Measuring range
- Linearity
- Repeatability
- Accuracy
(for M.V. from 1 to 10 m/s and -15 °C < medium T° with Stst. sensor < 130 °C
or 0 °C < medium T° with PVDF sensor < 80 °C)
* In the reference conditions, where: fluid = water, water and ambient temperatures = 20 °C,
upstream and downstream distances complied with, pipe dimensions adapted.
M.V. = measured value
General data
- Pressure class
- Fluid temperature
- with stainless steel sensor
- with PVDF sensor
- Minimum fluid conductivity
- Housing and cover material
- with stainless steel sensor
- with PVDF sensor
- Material of screws / seal / cable glands
- Materials in contact with the fluid
- Sensor armature
- Gaskets
- Electrodes
- Armature of electrodes
(stainless steel sensor)
- Earth ring (PVDF sensor)
8041
SPECIFICATIONS
Electromagnetic measurement
0,2 to 10 m/s
+/- (1% of the M.V. + 0.1% of the full scale)
0.25% of the M.V.
≤ +/-2% of the M.V., with calibration on site (for ex.
teach-in with a 8025 transmitter)
≤ +/-4% of the M.V., with standard K factor*.
Depends on the temperature and fitting
material (see 4.1.1)
-15 °C up to 150 °C (depending on fitting)
0 °C up to 80 °C (depending on fitting)
20 µS/cm
PPA, glass fiber reinforced
PC, glass fiber reinforced
stainless steel / EPDM / PA
stainless steel 316L (DIN 1.4404)
or PVDF
FKM (FDA agreement)
stainless steel 316L (DIN 1.4404)
PEEK (FDA agreement)
stainless steel 316L (DIN 1.4404)
33