4.1.2 Mounting positions
The flowmeter can be mounted in the following ways to obtain an accurate flow measure-
ment although the piping should be designed to ensure that the pipe is main tained full at
all times to avoid inaccurate measurement.
Mounting horizontally
Mounting vertically
- When mounting vertically ensure that the flow direction is in an
upward direction as indicated by the arrow.
- Always mount the flowmeter upstream a possible injection point in
the pipe of a high conductivity product (acid, base, saline,...).
It is advisable to mount the flowmeter at a 45° angle to the
horizontal centre of the pipe as shown in the diagram to
avoid having deposits on the electrodes and false
mea sure ments due to air bubbles.
INSTALLATION
Correct
Correct
22
In cor rect
In cor rect
45°
45°
8041