9.8.

description of the function

Function
Description of the function
EXT
To calibrate the expansion board in transmitters if it is activated (see Calibration Mode chap
Adjust the 4-20 mA output or the 4-20 mA input respectively:
Select
OUT
The transmitter generates a 4 mA current.
Using a multimeter, measure the current on the 4-20 mA output or input respectively.
Input this value in the function
Press ENTER to confirm.
The transmitter generates a 20 mA current.
Using a multimeter, measure the current on the 4-20 mA output or input respectively.
Input this value in the function
Confirm or do not confirm the input values by hitting "
SIM
To test the commutation thresholds by inputting a temperature value.
END
To go back to Read mode and display the temperature measured.
34
or
respectively and confirm.
IN
.
OFFS
.
SPAN